Electric Services, major discharger, Wilmington, North Carolina. NPDES permit NC0001422, in force until Mar 31, 2028. Last 12 months: over a limit 2 times (last May 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit |
|---|---|---|---|
| April 2026 | pH, daily maximum | 9.6 SU | ≤ 9 SU |
| May 2026 | pH, daily maximum | 9.4 SU | ≤ 9 SU |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | report only (deg C) | all year | 001 |
| Turbidity | daily maximum | report only (NTU) | all year | 001 |
| Oxygen, dissolved [DO] | daily maximum | report only (mg/L) | all year | 001 |
| pH | daily minimum | ≥ 6 SU | all year | 001 |
| pH | daily maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 001 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 001 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 001 |
| Nitrogen, total [as N] | daily maximum | report only (mg/L) | all year | 001 |
| Phosphorus, total [as P] | daily maximum | report only (mg/L) | all year | 001 |
| Hardness, total [as CaCO3] | daily maximum | report only (mg/L) | all year | 001 |
| Arsenic, total [as As] | daily maximum | report only (ug/L) | all year | 001 |
| Cadmium, total [as Cd] | daily maximum | report only (ug/L) | all year | 001 |
| Copper, total [as Cu] | daily maximum | report only (ug/L) | all year | 001 |
| Lead, total [as Pb] | daily maximum | report only (ug/L) | all year | 001 |
| Nickel, total [as Ni] | daily maximum | report only (ug/L) | all year | 001 |
| Zinc, total [as Zn] | daily maximum | report only (ug/L) | all year | 001 |
| Aluminum, total [as Al] | daily maximum | report only (mg/L) | all year | 001 |
| Selenium, total [as Se] | daily maximum | report only (ug/L) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Mercury, total [as Hg] | daily maximum | report only (ng/L) | all year | 001 |
| Temperature, water deg. centigrade | daily maximum | report only (deg C) | all year | 008 |
| Temperature, water deg. centigrade | 30-day average | ≤ 43 deg C | all year | 008 |
| Oxygen, dissolved [DO] | daily maximum | report only (mg/L) | all year | 008 |
| pH | daily minimum | ≥ 6 SU | all year | 008 |
| pH | daily maximum | ≤ 9 SU | all year | 008 |
| Solids, total suspended | 30-day average | ≤ 30 mg/L | all year | 008 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 008 |
| Oil & Grease | 30-day average | ≤ 15 mg/L | all year | 008 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 008 |
| Nitrogen, total [as N] | daily maximum | report only (mg/L) | all year | 008 |
| Phosphorus, total [as P] | daily maximum | report only (mg/L) | all year | 008 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 008 |
Cited limits by parameter: North Carolina's rules and the federal ones.
Same industry: the 20 Electric Services permits in North Carolina.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/NC0001422 · MCP: https://passage-data.com/mcp