Passage Data · Check a report · Use it from your AI

Kings Gate Club, Inc.

Water Supply, Nokomis, Florida. NPDES permit FL0188859, in force until Jan 27, 2028. Last 12 months: over a limit 4 times (last March 2026), 101 required values missing, 1 of 24 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 28 days after each period: form 1 monthly (5 values), form T monthly (6 values), form A yearly, form Q quarterly
Renewal application due
Jul 31, 2027 · 180 days before expiry; your permit may set another date
Last report on file
July 2026
Oct 2024 – Sep 2025
19 values over a limit, 68 required values missing, 12 of 22 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
October 2025Oxygen, dissolved percent saturation, 90% of samples88≤ 38 %132%
October 2025Oxygen, dissolved percent saturation, 90% of samples88≤ 38 %132%
November 2025Oxygen, dissolved percent saturation, 90% of samples80 %≤ 38 %111%
March 2026Oxygen, dissolved percent saturation, 90% of samples88≤ 38 %132%

Limits in force (21)

ParameterStatisticLimitMonths
Oxygen, dissolved percent saturation90% of samples≤ 38 %all year
pHdaily minimum≥ 6 SUall year
pHdaily maximum≤ 8.5 SUall year
Solids, total suspendeddaily maximumreport only (mg/L)all year
Solids, total suspendedannual average≤ 5 mg/Lall year
Nitrogen, total [as N]daily maximumreport only (mg/L)all year
Nitrogen, total [as N]annual average≤ 3 mg/Lall year
Phosphorus, total [as P]daily maximumreport only (mg/L)all year
Phosphorus, total [as P]annual average≤ 1 mg/Lall year
Radium 226 + radium 228, totaldaily maximumreport only (pCi/L)all year
Radium 226 + radium 228, totalannual average≤ 5 pCi/Lall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year
Alpha, gross particle activitymaximumreport only (pCi/L)all year
Alpha, gross particle activityannual average≤ 15 pCi/Lall year
LC50 Static Renewal 96Hr Acute Ceriodaphnia dubiaminimum≥ 100 %all year
LC50 Static Renewal 96Hr Acute Ceriodaphnia dubiaminimum≥ 100 %all year
LC50 Static Renewal 96Hr Acute Ceriodaphnia dubiaminimum≥ 100 %all year
LC50 Static Renewal 96Hr Acute Cyprinella leedsiminimum≥ 100 %all year
LC50 Static Renewal 96Hr Acute Cyprinella leedsiminimum≥ 100 %all year
LC50 Static Renewal 96Hr Acute Cyprinella leedsiminimum≥ 100 %all year

How strict are these limits?

Cited limits by parameter: Florida's rules and the federal ones.

Same industry: the 26 Water Supply permits in Florida.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/FL0188859 · MCP: https://passage-data.com/mcp