Water Supply, major discharger, Melbourne, Florida. NPDES permit FL0043443, in force until Jul 23, 2031. Last 12 months: over a limit 3 times (last May 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| January 2026 | Nitrogen, total [as N], daily maximum | 3.5 | ≤ 3 mg/L | 17% |
| January 2026 | Nitrogen, total [as N], monthly average | 3.5 | ≤ 3 mg/L | 17% |
| May 2026 | Oxygen, dissolved [DO], daily minimum | 4.92 | ≥ 5 mg/L | 2% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Temperature, water deg. centigrade | monthly average | report only (deg C) | all year |
| Specific conductance | monthly average | report only (umho/cm) | all year |
| Oxygen, dissolved [DO] | daily minimum | ≥ 5 mg/L | all year |
| pH | daily minimum | ≥ 6.5 SU | all year |
| pH | daily maximum | ≤ 8.5 SU | all year |
| Nitrogen, total [as N] | monthly average | ≤ 3 mg/L | all year |
| Nitrogen, total [as N] | daily maximum | ≤ 3 mg/L | all year |
| Nitrogen, total [as N] | annual total | ≤ 9170 lb/yr | all year |
| Nitrogen, total [as N] | monthly total | report only (lb/mo) | all year |
| Phosphorus, total [as P] | monthly average | ≤ 1 mg/L | all year |
| Phosphorus, total [as P] | daily maximum | ≤ 1 mg/L | all year |
| Phosphorus, total [as P] | annual total | ≤ 195 lb/yr | all year |
| Phosphorus, total [as P] | monthly total | report only (lb/mo) | all year |
| Radium 226 + radium 228, total | daily maximum | ≤ 36 pCi/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | ≤ 1.25 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 1.25 MGD | all year |
| Hydrogen sulfide, unionized | daily maximum | report only (mg/L) | all year |
| Alpha, gross particle activity | daily maximum | ≤ 86 pCi/L | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 40 % | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 40 % | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 40 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 40 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 40 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 40 % | all year |