Passage Data · Check a report · Use it from your AI
Water Supply, Punta Gorda, Florida. NPDES permit FL0035378, in force until Aug 27, 2029. Last 12 months: over a limit 8 times (last September 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Flow, in conduit or thru treatment plant, daily maximum | .203 MGD | ≤ .15 MGD | 35% |
| April 2026 | Oxygen, dissolved percent saturation, minimum weekly average | 0 | ≥ 51 % | 100% |
| April 2026 | Oxygen, dissolved percent saturation, minimum weekly average | 0 | ≥ 51 % | 100% |
| April 2026 | Oxygen, dissolved percent saturation, monthly average minimum | 0 | ≥ 56 % | 100% |
| April 2026 | Oxygen, dissolved percent saturation, monthly average minimum | 0 | ≥ 56 % | 100% |
| April 2026 | pH, minimum | 0 | ≥ 6.5 SU | — |
| August 2026 | Flow, in conduit or thru treatment plant, daily maximum | .205 | ≤ .15 MGD | 37% |
| September 2026 | Alpha, gross particle activity, maximum | 190 | ≤ 180.9 pCi/L | 5% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved percent saturation | monthly average minimum | ≥ 56 % | all year |
| Oxygen, dissolved percent saturation | minimum weekly average | ≥ 51 % | all year |
| Oxygen, dissolved percent saturation | monthly average minimum | ≥ 56 % | all year |
| Oxygen, dissolved percent saturation | minimum weekly average | ≥ 51 % | all year |
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Nitrogen, total [as N] | monthly total | ≤ 72.7 lb/mo | all year |
| Nitrogen, total [as N] | maximum | report only (mg/L) | all year |
| Phosphorus, total [as P] | maximum | report only (mg/L) | all year |
| Phosphorus, total [as P] | annual average | ≤ .5 mg/L | all year |
| Chloride [as Cl] | maximum | report only (mg/L) | all year |
| Fluoride, total [as F] | maximum | ≤ 6.3 mg/L | all year |
| Copper, total recoverable | maximum | ≤ 3.7 ug/L | all year |
| Radium 226 + radium 228, total | maximum | ≤ 100.4 pCi/L | all year |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .15 MGD | all year |
| Bromide [as Br] | maximum | report only (mg/L) | all year |
| Alpha, gross particle activity | maximum | ≤ 180.9 pCi/L | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 50 % | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 50 % | all year |
| IC25 Lethal Static Renewal 7 Day Chronic Menidia beryllina | minimum | ≥ 50 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 50 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 50 % | all year |
| IC25 Static Renewal 7 Day Chronic Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 50 % | all year |
Cited limits by parameter: Florida's rules and the federal ones.
Same industry: the 26 Water Supply permits in Florida.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/FL0035378 · MCP: https://passage-data.com/mcp