Venice, City of

Water Supply, major discharger, Venice, Florida. NPDES permit FL0035335, in force until Feb 9, 2031. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 90 days after each period: form 1 monthly (40 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 0 of 12 reports late

Limits in force (40)

ParameterStatisticLimitMonths
Color [PT-CO units]maximumreport only (col unit (pc))all year
Specific conductancemaximumreport only (umho/cm)all year
Oxygen, dissolved [DO]daily average minimum≥ 5 mg/Lall year
Oxygen, dissolved percent saturationweekly minimum≥ 51 %all year
Oxygen, dissolved percent saturationdaily minimum≥ 42 %all year
Oxygen, dissolved percent saturationminimum annual average≥ 56 %all year
pHminimum≥ 6.5 SUall year
pHmaximum≤ 8.5 SUall year
Nitrogen, total [as N]monthly total≤ 1011 lb/moall year
Nitrogen, total [as N]annual average≤ 23.2 lb/dall year
Nitrogen, organic total [as N]maximumreport only (mg/L)all year
Nitrogen, ammonia total [as N]maximumreport only (mg/L)all year
Nitrogen, nitrite total [as N]maximumreport only (mg/L)all year
Nitrogen, nitrate total [as N]maximumreport only (mg/L)all year
Phosphorus, total [as P]monthly total≤ 174 lb/moall year
Phosphorus, total [as P]annual average≤ 3.6 lb/dall year
Calcium, total recoverablemaximumreport only (mg/L)all year
Magnesium, total recoverablemaximumreport only (mg/L)all year
Sodium, total recoverablemaximumreport only (mg/L)all year
Potassium, total [as K]maximumreport only (mg/L)all year
Chloride [as Cl]maximumreport only (mg/L)all year
Fluoride, total [as F]maximum≤ 6 mg/Lall year
Iron, total recoverablemaximum≤ .3 mg/Lall year
Aluminum, total recoverablemaximum≤ 1.5 mg/Lall year
Copper, total recoverablemaximum≤ 5 ug/Lall year
Radium 226 + radium 228, totalmaximum≤ 25 pCi/Lall year
Flow, in conduit or thru treatment plantmonthly average≤ 3.42 MGDall year
Chlorine, total residualmaximum≤ .01 mg/Lall year
Solids, total dissolvedmaximumreport only (mg/L)all year
Phosphorous, in total orthophosphatemaximumreport only (mg/L)all year
Nitrogen, ammonia total [as NH4]maximumreport only (mg/L)all year
Bromide [as Br]maximumreport only (mg/L)all year
Hydrogen sulfidemaximumreport only (mg/L)all year
Alpha, gross particle activitymaximum≤ 65 pCi/Lall year
LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 30 %all year
LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 30 %all year
LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia)minimum≥ 30 %all year
LC50 Static Renewal 96Hr Acute Menidiaminimum≥ 30 %all year
LC50 Static Renewal 96Hr Acute Menidiaminimum≥ 30 %all year
LC50 Static Renewal 96Hr Acute Menidiaminimum≥ 30 %all year

How strict are these limits?

Cited limits by parameter: Florida's rules and the federal ones.

Same industry: the 26 Water Supply permits in Florida.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/FL0035335 · MCP: https://passage-data.com/mcp