Passage Data · Check a report · Use it from your AI
Water Supply, major discharger, Venice, Florida. NPDES permit FL0035335, in force until Feb 9, 2031. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Color [PT-CO units] | maximum | report only (col unit (pc)) | all year |
| Specific conductance | maximum | report only (umho/cm) | all year |
| Oxygen, dissolved [DO] | daily average minimum | ≥ 5 mg/L | all year |
| Oxygen, dissolved percent saturation | weekly minimum | ≥ 51 % | all year |
| Oxygen, dissolved percent saturation | daily minimum | ≥ 42 % | all year |
| Oxygen, dissolved percent saturation | minimum annual average | ≥ 56 % | all year |
| pH | minimum | ≥ 6.5 SU | all year |
| pH | maximum | ≤ 8.5 SU | all year |
| Nitrogen, total [as N] | monthly total | ≤ 1011 lb/mo | all year |
| Nitrogen, total [as N] | annual average | ≤ 23.2 lb/d | all year |
| Nitrogen, organic total [as N] | maximum | report only (mg/L) | all year |
| Nitrogen, ammonia total [as N] | maximum | report only (mg/L) | all year |
| Nitrogen, nitrite total [as N] | maximum | report only (mg/L) | all year |
| Nitrogen, nitrate total [as N] | maximum | report only (mg/L) | all year |
| Phosphorus, total [as P] | monthly total | ≤ 174 lb/mo | all year |
| Phosphorus, total [as P] | annual average | ≤ 3.6 lb/d | all year |
| Calcium, total recoverable | maximum | report only (mg/L) | all year |
| Magnesium, total recoverable | maximum | report only (mg/L) | all year |
| Sodium, total recoverable | maximum | report only (mg/L) | all year |
| Potassium, total [as K] | maximum | report only (mg/L) | all year |
| Chloride [as Cl] | maximum | report only (mg/L) | all year |
| Fluoride, total [as F] | maximum | ≤ 6 mg/L | all year |
| Iron, total recoverable | maximum | ≤ .3 mg/L | all year |
| Aluminum, total recoverable | maximum | ≤ 1.5 mg/L | all year |
| Copper, total recoverable | maximum | ≤ 5 ug/L | all year |
| Radium 226 + radium 228, total | maximum | ≤ 25 pCi/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | ≤ 3.42 MGD | all year |
| Chlorine, total residual | maximum | ≤ .01 mg/L | all year |
| Solids, total dissolved | maximum | report only (mg/L) | all year |
| Phosphorous, in total orthophosphate | maximum | report only (mg/L) | all year |
| Nitrogen, ammonia total [as NH4] | maximum | report only (mg/L) | all year |
| Bromide [as Br] | maximum | report only (mg/L) | all year |
| Hydrogen sulfide | maximum | report only (mg/L) | all year |
| Alpha, gross particle activity | maximum | ≤ 65 pCi/L | all year |
| LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 30 % | all year |
| LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 30 % | all year |
| LC50 Static Renewal 96Hr Acute Americamysis bahia (formerly Mysidopsis bahia) | minimum | ≥ 30 % | all year |
| LC50 Static Renewal 96Hr Acute Menidia | minimum | ≥ 30 % | all year |
| LC50 Static Renewal 96Hr Acute Menidia | minimum | ≥ 30 % | all year |
| LC50 Static Renewal 96Hr Acute Menidia | minimum | ≥ 30 % | all year |
Cited limits by parameter: Florida's rules and the federal ones.
Same industry: the 26 Water Supply permits in Florida.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/FL0035335 · MCP: https://passage-data.com/mcp