Passage Data · Cited limits by place · Use it from your AI

Copper in Texas (US-TX): 40 CFR Part 423 — Steam electric power generating point source category

11 rows for copper in this instrument. Every instrument for copper in Texas

United States (US): 11 rows

Effluent: 11 rows

40 CFR Part 423 — Steam electric power generating point source category · eCFR as of 2026-10-05 · 11 limits
ParameterValueStatisticApplies whenCite
Copper, total1.0 mg/Ldaily maximumdischarge to surface water
existing sources (BPT)
(5) The quantity of pollutants discharged in metal cleaning wastes shall not exceed the quantity determined by multiplying the flow of metal cleaning wastes times the concentration listed in the following table:
40 CFR 423.12 (BPT)
Copper, total 1.0 1.0
Copper, total1.0 mg/Lmonthly averageas aboveas above
Copper, total1.0 mg/Ldaily maximumdischarge to surface water
existing sources (BAT)
(e) The quantity of pollutants discharged in chemical metal cleaning wastes shall not exceed the quantity determined by multiplying the flow of chemical metal cleaning wastes times the concentration listed in the following table:
40 CFR 423.13 (BAT)
Copper, total 1.0 1.0
Copper, total1.0 mg/Lmonthly averageas aboveas above
Copper, total1.0 mg/Ldaily maximumdischarge to surface water
new sources (NSPS)
(4) Chemical metal cleaning wastes. The quantity of pollutants discharged in chemical metal cleaning wastes shall not exceed the quantity determined by multiplying the flow of chemical metal cleaning wastes times the concentration listed in the following table:
40 CFR 423.15 (NSPS)
Copper, total 1.0 1.0
Copper, total1.0 mg/Lmonthly averageas aboveas above
Copper, total1.0 mg/Ldaily maximumas aboveas above
Copper, total1.0 mg/Lmonthly averageas aboveas above
Copper, total1.0 mg/Ldaily maximumdischarge to a sewer (pretreatment)
existing sources (PSES)
(b) The pollutants discharged in chemical metal cleaning wastes shall not exceed the concentration listed in the following table:
40 CFR 423.16 (PSES)
Copper, total 1.0
Copper, total1.0 mg/Ldaily maximumdischarge to a sewer (pretreatment)
new sources (PSNS)
(2) Chemical metal cleaning wastes. The pollutants discharged in chemical metal cleaning wastes shall not exceed the concentration listed in the following table:
40 CFR 423.17 (PSNS)
Copper, total 1.0
Copper, total1.0 mg/Ldaily maximumas aboveas above

Read from public law and public agency files. A row missing here is missing from our sources, not from the law of the place. Check the cited source before relying on a value.