The Dickirson Corporation

Oil And Gas Field Machinery, Ripley, West Virginia. NPDES permit WV0116092, in force until Mar 12, 2028. Last 12 months: over a limit 8 times (last June 2026), 3 of 14 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 25 days after each period: outfall 001 form A monthly (15 values), outfall 001 form D yearly, outfall 002 form C twice a year
Renewal application due
Sep 14, 2027 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
3 values over a limit, 15 required values missing, 2 of 15 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
November 2025Aluminum, total recoverable, daily maximum.91 mg/L≤ .75 mg/L21%
November 2025Iron, total [as Fe], daily maximum2.1 mg/L≤ 1.5 mg/L40%
May 2026Aluminum, total recoverable, daily maximum1.4 mg/L≤ .75 mg/L87%
May 2026Iron, total [as Fe], daily maximum2.7 mg/L≤ 1.5 mg/L80%
May 2026Solids, total suspended, daily maximum136 mg/L≤ 120 mg/L13%
June 2026Aluminum, total recoverable, daily maximum1.9 mg/L≤ .75 mg/L153%
June 2026Iron, total [as Fe], daily maximum3.4 mg/L≤ 1.5 mg/L127%
June 2026Solids, total suspended, daily maximum197 mg/L≤ 120 mg/L64%

Limits in force (31)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]instantaneous minimum≥ 6 mg/Lall year001
pHinstantaneous minimum≥ 6 SUall year001
pHinstantaneous maximum≤ 9 SUall year001
Solids, total suspendedmonthly averagereport only (mg/L)all year001
Solids, total suspendeddaily maximum≤ 120 mg/Lall year001
Oil and grease, hexane extr methodmonthly averagereport only (mg/L)all year001
Oil and grease, hexane extr methoddaily maximum≤ 4.2 mg/Lall year001
Iron, total [as Fe]monthly averagereport only (mg/L)all year001
Iron, total [as Fe]daily maximum≤ 1.5 mg/Lall year001
Aluminum, total recoverablemonthly averagereport only (mg/L)all year001
Aluminum, total recoverabledaily maximum≤ .75 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Organics, total toxic [TTO]monthly averagereport only (mg/L)all year001
Organics, total toxic [TTO]daily maximumreport only (mg/L)all year001
Chemical Oxygen Demand [COD]monthly averagereport only (mg/L)all year001
Chemical Oxygen Demand [COD]daily maximumreport only (mg/L)all year001
pHinstantaneous minimumreport only (SU)all year002
pHinstantaneous maximumreport only (SU)all year002
Solids, total suspendedmonthly averagereport only (mg/L)all year002
Solids, total suspendeddaily maximumreport only (mg/L)all year002
Oil and grease, hexane extr methodmonthly averagereport only (mg/L)all year002
Oil and grease, hexane extr methoddaily maximumreport only (mg/L)all year002
Iron, total [as Fe]monthly averagereport only (mg/L)all year002
Iron, total [as Fe]daily maximumreport only (mg/L)all year002
Aluminum, total recoverablemonthly averagereport only (mg/L)all year002
Aluminum, total recoverabledaily maximumreport only (mg/L)all year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
Chemical Oxygen Demand [COD]monthly averagereport only (mg/L)all year002
Chemical Oxygen Demand [COD]daily maximumreport only (mg/L)all year002

How strict are these limits?

Cited limits by parameter: West Virginia's rules and the federal ones.

Same industry: the 3 Industrial and Commercial Machinery and Computer Equipment permits in West Virginia.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/WV0116092 · MCP: https://passage-data.com/mcp