Passage Data · Check a report · Use it from your AI

Gauley River Power Partners

Electric Services, Summerville, West Virginia. NPDES permit WV0114847, in force until Oct 18, 2027. Last 12 months: over a limit 3 times (last June 2026), 12 required values missing, 9 of 37 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 25 days after each period: outfall 001 form A monthly (8 values), outfall 002 form A monthly (8 values), outfall 003 form A monthly (8 values), outfall 003 form B quarterly (8 values), outfall 003 form D yearly
Renewal application due
Apr 21, 2027 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 0 of 42 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
May 2026Zinc, total recoverable, monthly average.104 mg/L≤ .044 mg/L136%
June 2026Copper, total recoverable, daily maximum.031 mg/L≤ .014 mg/L121%
June 2026Copper, total recoverable, monthly average.031 mg/L≤ .007 mg/L343%

Limits in force (34)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year001
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year001
Temp. diff. between samp. & upstrm deg. Fmonthly averagereport only (deg F)all year001
Temp. diff. between samp. & upstrm deg. Fdaily maximumreport only (deg F)all year001
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year002
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year002
Temperature, water deg. fahrenheitmonthly averagereport only (deg F)all year002
Temperature, water deg. fahrenheitdaily maximumreport only (deg F)all year002
Temp. diff. between samp. & upstrm deg. Fmonthly averagereport only (deg F)all year002
Temp. diff. between samp. & upstrm deg. Fdaily maximumreport only (deg F)all year002
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year002
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year002
pHinstantaneous minimum≥ 6 SUall year003
pHinstantaneous maximum≤ 9 SUall year003
Solids, total suspendedmonthly average≤ 10 mg/Lall year003
Solids, total suspendedmonthly average≤ 10 mg/Lall year003
Solids, total suspendeddaily maximum≤ 22 mg/Lall year003
Solids, total suspendeddaily maximum≤ 22 mg/Lall year003
Oil and grease, hexane extr methodmonthly average≤ 3 mg/Lall year003
Oil and grease, hexane extr methodmonthly average≤ 3 mg/Lall year003
Oil and grease, hexane extr methoddaily maximum≤ 6 mg/Lall year003
Oil and grease, hexane extr methoddaily maximum≤ 6 mg/Lall year003
Zinc, total recoverablemonthly average≤ .044 mg/Lall year003
Zinc, total recoverabledaily maximum≤ .12 mg/Lall year003
Lead, total recoverablemonthly averagereport only (mg/L)all year003
Lead, total recoverabledaily maximumreport only (mg/L)all year003
Copper, total recoverablemonthly average≤ .007 mg/Lall year003
Copper, total recoverabledaily maximum≤ .014 mg/Lall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003

How strict are these limits?

Cited limits by parameter: West Virginia's rules and the federal ones.

Same industry: the 24 Electric Services permits in West Virginia.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/WV0114847 · MCP: https://passage-data.com/mcp