Passage Data · Check a report · Use it from your AI

Town of West Rutland

Sewage treatment plant, major discharger, West Rutland, Vermont. NPDES permit VT0100714, in force until Sep 30, 2027. Last 12 months: over a limit once (last April 2026), 18 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 15 days after each period: form A monthly (18 values)
Renewal application due
Apr 3, 2027 · 180 days before expiry; your permit may set another date
Last report on file
July 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
April 2026E. coli, thermotol, MF, MTEC, instantaneous maximum2400≤ 406 #/100mL491%

Limits in force (25)

ParameterStatisticLimitMonths
Oxygen demand, ultimatedaily maximum≤ 205 lb/dJun–Sep
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/LJun–Sep
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/LJan, Feb, Mar, Apr, May, Oct, Nov, Dec
BOD, 5-day, 20 deg. Cweekly average≤ 45 mg/LJun–Sep
BOD, 5-day, 20 deg. Cweekly average≤ 45 mg/LJan, Feb, Mar, Apr, May, Oct, Nov, Dec
BOD, 5-day, 20 deg. Cdaily maximum≤ 50 mg/LJun–Sep
BOD, 5-day, 20 deg. Cdaily maximum≤ 50 mg/LJan, Feb, Mar, Apr, May, Oct, Nov, Dec
BOD, 5-day, 20 deg. Cmonthly average≤ 62.5 lb/dJun–Sep
BOD, 5-day, 20 deg. Cmonthly average≤ 62.5 lb/dJan, Feb, Mar, Apr, May, Oct, Nov, Dec
BOD, 5-day, 20 deg. Cweekly average≤ 93.8 lb/dJun–Sep
BOD, 5-day, 20 deg. Cweekly average≤ 93.8 lb/dJan, Feb, Mar, Apr, May, Oct, Nov, Dec
pHminimum≥ 6.5 SUall year
pHmaximum≤ 8.5 SUall year
Solids, total suspendedmonthly average≤ 30 mg/Lall year
Solids, total suspendedweekly average≤ 45 mg/Lall year
Solids, total suspendeddaily maximum≤ 50 mg/Lall year
Solids, total suspendedmonthly average≤ 62.5 lb/dall year
Solids, total suspendedweekly average≤ 93.8 lb/dall year
Solids, settleableinstantaneous maximum≤ 1 mL/Lall year
Phosphorus, total [as P]monthly average≤ .8 mg/Lall year
Phosphorus, total [as P]annual total≤ 802 lb/yrDec
E. coli, thermotol, MF, MTECinstantaneous maximum≤ 406 #/100mLall year
Flow, in conduit or thru treatment plantannual average≤ .45 MGDDec
BOD, 5-day, percent removalmonthly minimum≥ 85 %all year
Solids, suspended percent removalmonthly minimum≥ 85 %all year

How strict are these limits?

Cited limits by parameter: Vermont's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/VT0100714 · MCP: https://passage-data.com/mcp