St. Croix Renaissance Group

NPDES permit VI0050024 · Major NON-POTW · expired, expires 2018-02-28 · EPA's file as of 2026-09-19

Check this month's numbers before you file
Watch this permit — $79 a month. Every Monday, from EPA's newest files: the next report due and when, whether EPA's file holds your last one, any change to this permit's limits or status, and the renewal date.

This permit expired on 2018-02-28 and is expired: its last limits keep applying until a new permit is issued, and EPA still expects the reports.

EPA's record, 2025-09-01 to 2026-08-31

0values over a limit
0required values missing, on 0 form(s)
11of 130 forms filed late

Last period with anything received: 2026-08-17.

Reporting

Reports are due about 28 days after each monitoring period ends (read off this permit's own late-day counts in EPA's filings).

Limits in force (106)

OutfallParameterStatisticLimitMonths
001Temperature, water deg. centigradeDAILY MX <= 32 deg C all year
001Temperature, water deg. centigradeDAILY MX <= 32 deg C all year
001Oxygen, dissolved [DO]MINIMUM >= 5 mg/L all year
001pHMINIMUM >= 6.7 SU all year
001pHMAXIMUM <= 8.5 SU all year
001Nitrogen, total [as N]MAXIMUM report only all year
001Phosphorous, total organic [as P]MAXIMUM report only all year
001Magnesium, total [as Mg]MAXIMUM report only all year
001Barium, total [as Ba]MAXIMUM report only all year
001Boron, total [as B]MAXIMUM report only all year
001Copper, total [as Cu]MAXIMUM report only all year
001Manganese, total [as Mn]MAXIMUM report only all year
001Zinc, total [as Zn]MAXIMUM report only all year
001Aluminum, total [as Al]MAXIMUM report only all year
001Whole effluent toxicityMAXIMUM report only all year
001Flow, in conduit or thru treatment plantMO AVG report only all year
001Flow, in conduit or thru treatment plantDAILY MX report only all year
001Chlorine, total residualMO AVG <= 6.1 ug/d all year
001Chlorine, total residualDAILY MX <= 12.3 ug/d all year
001Iron, total [as Fe]MAXIMUM report only all year
002Iron, total [as Fe]DAILY MX <= 1 mg/L all year
002Storm water flowDAILY MX report only all year
A01pHMINIMUM >= 6 SU all year
A01pHMAXIMUM <= 9 SU all year
A01Solids, total suspendedMO AVG <= 30 mg/L all year
A01Solids, total suspendedDAILY MX <= 100 mg/L all year
A01Oil & GreaseMO AVG <= 15 mg/L all year
A01Oil & GreaseDAILY MX <= 20 mg/L all year
A01Flow, in conduit or thru treatment plantMO AVG report only all year
A01Flow, in conduit or thru treatment plantDAILY MX report only all year
B01Flow, in conduit or thru treatment plantMO AVG report only all year
B01Flow, in conduit or thru treatment plantDAILY MX report only all year
B01Chlorine, total residualDAILY MX <= .02 mg/L all year
C01pHMINIMUM >= 6 SU all year
C01pHMAXIMUM <= 9 SU all year
C01Solids, total suspendedMO AVG <= 30 mg/L all year
C01Solids, total suspendedDAILY MX <= 100 mg/L all year
C01Oil & GreaseMO AVG <= 15 mg/L all year
C01Oil & GreaseDAILY MX <= 20 mg/L all year
C01Copper, total [as Cu]MO AVG <= 1 mg/L all year
C01Copper, total [as Cu]DAILY MX <= 1 mg/L all year
C01Iron, total [as Fe]MO AVG <= 1 mg/L all year
C01Iron, total [as Fe]DAILY MX <= 1 mg/L all year
C01Flow, in conduit or thru treatment plantMO AVG report only all year
C01Flow, in conduit or thru treatment plantDAILY MX report only all year
D01pHMINIMUM >= 6 SU all year
D01pHMAXIMUM <= 9 SU all year
D01Solids, total suspendedDAILY MX <= 50 mg/L all year
D01Flow, in conduit or thru treatment plantDAILY MX report only all year
E01Flow, in conduit or thru treatment plantMO AVG report only all year
E01Flow, in conduit or thru treatment plantDAILY MX report only all year
F01Flow, in conduit or thru treatment plantMO AVG report only all year
F01Flow, in conduit or thru treatment plantDAILY MX report only all year
G01ColorVALUE report only all year
G01Odor [Threshold Number]VALUE report only all year
G01BOD, 5-day, 20 deg. CMO AVG report only all year
G01BOD, 5-day, 20 deg. CMAXIMUM <= 54.1 lb/d all year
G01pHMINIMUM report only all year
G01pHMAXIMUM report only all year
G01Nitrogen, total [as N]MAXIMUM report only all year
G01Phosphorous, total organic [as P]MAXIMUM <= 16.6 lb/d all year
G01Magnesium, total [as Mg]MAXIMUM report only all year
G01Sulfate, total [as SO4]MAXIMUM report only all year
G01Arsenic, total [as As]MAXIMUM report only all year
G01Barium, total [as Ba]MAXIMUM report only all year
G01Boron, total [as B]MAXIMUM report only all year
G01Copper, total [as Cu]MAXIMUM <= .9 lb/d all year
G01Lead, total [as Pb]MAXIMUM report only all year
G01Manganese, total [as Mn]MAXIMUM report only all year
G01Manganese, total [as Mn]MAXIMUM report only all year
G01Nickel, total [as Ni]MAXIMUM report only all year
G01Silver, total [as Ag]MAXIMUM report only all year
G01Zinc, total [as Zn]MAXIMUM report only all year
G01Aluminum, total [as Al]MAXIMUM report only all year
G01Selenium, total [as Se]MAXIMUM report only all year
G01Flow, in conduit or thru treatment plantMO AVG report only all year
G01Flow, in conduit or thru treatment plantMAXIMUM report only all year
G01Mercury, total [as Hg]MAXIMUM report only all year
G01Iron, total [as Fe]MAXIMUM report only all year
J01ColorMAXIMUM report only all year
J01Odor [Threshold Number]MAXIMUM report only all year
J01BOD, 5-day, 20 deg. CMAXIMUM report only all year
J01pHMINIMUM report only all year
J01pHMAXIMUM report only all year
J01Flow, in conduit or thru treatment plantWKLY AVG report only all year
J01Flow, in conduit or thru treatment plantMAXIMUM <= 50 gal/min all year
J01Chemical Oxygen Demand [COD]MAXIMUM report only all year
K01ColorMAXIMUM report only all year
K01Odor [Threshold Number]MAXIMUM report only all year
K01BOD, 5-day, 20 deg. CMO AVG report only all year
K01BOD, 5-day, 20 deg. CMAXIMUM <= 925 lb/d all year
K01pHMINIMUM report only all year
K01pHMAXIMUM report only all year
K01Nitrogen, total [as N]MAXIMUM report only all year
K01Phosphorous, total organic [as P]MAXIMUM <= 5 mg/L all year
K01Magnesium, total [as Mg]MAXIMUM report only all year
K01Sulfate, total [as SO4]MAXIMUM report only all year
K01Arsenic, total [as As]MAXIMUM report only all year
K01Iron, total [as Fe]MAXIMUM report only all year
K01Thallium, total [as Tl]MAXIMUM report only all year
K01Zinc, total [as Zn]MAXIMUM report only all year
K01Selenium, total [as Se]MAXIMUM report only all year
K01Flow, in conduit or thru treatment plantMO AVG report only all year
K01Flow, in conduit or thru treatment plantMAXIMUM report only all year
K01Chemical Oxygen Demand [COD]MO AVG report only all year
K01Chemical Oxygen Demand [COD]MAXIMUM <= 2700 lb/d all year

Built from EPA's ECHO bulk files. EPA's file, not the permit document, is the source: read your permit. Check a report before you file it · All states