Passage Data · Check a report · Use it from your AI
Electric Services, major discharger, New Canton, Virginia. NPDES permit VA0090891 expired Nov 16, 2014; its limits still apply. Last 12 months: over a limit once (last December 2025). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit |
|---|---|---|---|
| December 2025 | pH, maximum | 9.9 | ≤ 9 SU |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. centigrade | daily maximum | ≤ 32 deg C | all year | 001 |
| pH | daily minimum | ≥ 6 SU | all year | 001 |
| pH | daily maximum | ≤ 9 SU | all year | 001 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 001 |
| Chlorine, total residual | monthly average | ≤ .23 mg/L | all year | 001 |
| Chlorine, total residual | daily maximum | ≤ .47 mg/L | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | maximum | ≤ 9 SU | all year | 002 |
| Solids, total suspended | maximum | report only (mg/L) | all year | 002 |
| Iron, total recoverable | daily maximum | report only (mg/L) | all year | 002 |
| Petrol hydrocarbons, total recoverable | maximum | report only (mg/L) | all year | 002 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 002 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 002 |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year | 101 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 101 |
| Oil & Grease | monthly average | ≤ 15 mg/L | all year | 101 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 101 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 101 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 101 |
| Chromium, total [as Cr] | monthly average | ≤ .2 mg/L | all year | 102 |
| Chromium, total [as Cr] | daily maximum | ≤ .2 mg/L | all year | 102 |
| Zinc, total [as Zn] | monthly average | ≤ 1 mg/L | all year | 102 |
| Zinc, total [as Zn] | daily maximum | ≤ 1 mg/L | all year | 102 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 102 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 102 |
| Chlorine, free available | monthly average | ≤ .2 mg/L | all year | 102 |
| Chlorine, free available | daily maximum | ≤ .5 mg/L | all year | 102 |
Cited limits by parameter: Virginia's rules and the federal ones.
Same industry: the 24 Electric Services permits in Virginia.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/VA0090891 · MCP: https://passage-data.com/mcp