Rocky Mount Town

Sewage treatment plant, major discharger, Rocky Mount, Virginia. NPDES permit VA0085952, in force until Nov 30, 2026. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 10 days after each period: outfall 001 form M1 monthly (14 values), outfall 001 form Q1 quarterly, outfall 003 form S1 twice a year
Renewal application due
Jun 3, 2026 · 180 days before expiry; your permit may set another date
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 18 reports late

Limits in force (24)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]daily minimum≥ 6 mg/Lall year001
BOD, 5-day, 20 deg. Cmonthly average≤ 17.5 mg/Lall year001
BOD, 5-day, 20 deg. Cmaximum weekly average≤ 19.9 mg/Lall year001
BOD, 5-day, 20 deg. Cmonthly average≤ 133 kg/dall year001
BOD, 5-day, 20 deg. Cmaximum weekly average≤ 151 kg/dall year001
BOD, 5-day, 20 deg. Cminimumreport only (mg/L)all year001
pHdaily minimum≥ 6 SUall year001
pHdaily maximum≤ 9 SUall year001
Solids, total suspendedmonthly average≤ 30 mg/Lall year001
Solids, total suspendedmaximum weekly average≤ 45 mg/Lall year001
Solids, total suspendedmonthly average≤ 227 kg/dall year001
Solids, total suspendedmaximum weekly average≤ 340 kg/dall year001
Solids, total suspendedminimumreport only (mg/L)all year001
Nitrogen, ammonia total [as N]monthly average≤ 2.84 mg/Lall year001
Nitrogen, ammonia total [as N]maximum weekly average≤ 2.84 mg/Lall year001
Flow, in conduit or thru treatment plantmonthly average≤ 2 MGD (alert, not enforceable)all year001
Flow, in conduit or thru treatment plantmonthly maximumreport only (MGD) (alert, not enforceable)all year001
BOD, percent removal [total]minimum≥ 85 %all year001
E. coligeometric mean≤ 126 #/100mLall year001
Solids, suspended percent removalminimum≥ 85 %all year001
pHsingle samplereport only (SU)all year003
Solids, total suspendedsingle samplereport only (mg/L)all year003
E. colisingle sample≤ 235 #/100mLall year003
Precipitation volumeevent totalreport only (Mgal)all year003

How strict are these limits?

Cited limits by parameter: Virginia's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/VA0085952 · MCP: https://passage-data.com/mcp