Passage Data · Check a report · Use it from your AI
Electric Services, Hopewell, Virginia. NPDES permit VA0079502, in force until Feb 28, 2031. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. centigrade | maximum | ≤ 75 deg C | all year | 001 |
| Oxygen, dissolved [DO] | minimum | ≥ 5 mg/L | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Phosphorus, total [as P] | minimum | report only (mg/L) | all year | 001 |
| Phosphorus, total [as P] | monthly average | report only (mg/L) | all year | 001 |
| Hardness, total [as CaCO3] | monthly average | report only (mg/L) | all year | 001 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 001 |
| Flow, in conduit or thru treatment plant | maximum | report only (MGD) | all year | 001 |
| Chlorine, total residual | monthly average | ≤ 176 ug/L | all year | 001 |
| Chlorine, total residual | maximum | ≤ 176 ug/L | all year | 001 |
| Chromium, total [as Cr] | monthly average | ≤ .2 mg/L | all year | 101 |
| Chromium, total [as Cr] | maximum | ≤ .2 mg/L | all year | 101 |
| Zinc, total [as Zn] | monthly average | ≤ 1 mg/L | all year | 101 |
| Zinc, total [as Zn] | maximum | ≤ 1 mg/L | all year | 101 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 101 |
| Flow, in conduit or thru treatment plant | maximum | report only (MGD) | all year | 101 |
| Chlorine, free available | monthly average | ≤ .2 mg/L | all year | 101 |
| Chlorine, free available | maximum | ≤ .5 mg/L | all year | 101 |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year | 102 |
| Solids, total suspended | maximum | ≤ 100 mg/L | all year | 102 |
| Oil & Grease | monthly average | ≤ 15 mg/L | all year | 102 |
| Oil & Grease | maximum | ≤ 20 mg/L | all year | 102 |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year | 102 |
| Flow, in conduit or thru treatment plant | maximum | report only (MGD) | all year | 102 |
| pH | minimum | report only (SU) | all year | 902 |
| pH | maximum | report only (SU) | all year | 902 |
| Chlorine, total residual | maximum | report only (ug/L) | all year | 902 |
| Precipitation volume | monthly average | report only (Mgal) | all year | 902 |
| Precipitation volume | maximum | report only (Mgal) | all year | 902 |
| Parameter | New limit | New or tighter | Median, last 12 months | × new limit |
|---|---|---|---|---|
| Chlorine, total residual, maximum | 19 ug/L | tighter | 80 ug/L (11 values) | 4.21× |
| Chlorine, total residual, monthly average | 9.4 ug/L | tighter | 30 ug/L (11 values) | 3.19× |
Cited limits by parameter: Virginia's rules and the federal ones.
Same industry: the 24 Electric Services permits in Virginia.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/VA0079502 · MCP: https://passage-data.com/mcp