Passage Data · Check a report · Use it from your AI
Water Supply, Gloucester, Virginia. NPDES permit VA0078778, in force until Apr 30, 2030. Last 12 months: over a limit 14 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| January 2026 | Chloride [as Cl], daily maximum | 4944 | ≤ 390 mg/L | 1168% |
| January 2026 | Chloride [as Cl], monthly average | 4944 | ≤ 390 mg/L | 1168% |
| March 2026 | Chloride [as Cl], daily maximum | 5053 | ≤ 390 mg/L | 1196% |
| March 2026 | Chloride [as Cl], monthly average | 5053 | ≤ 390 mg/L | 1196% |
| April 2026 | Chloride [as Cl], daily maximum | 5136 | ≤ 390 mg/L | 1217% |
| April 2026 | Chloride [as Cl], monthly average | 5136 | ≤ 390 mg/L | 1217% |
| May 2026 | Chloride [as Cl], daily maximum | 5454 | ≤ 390 mg/L | 1298% |
| May 2026 | Chloride [as Cl], monthly average | 5454 | ≤ 390 mg/L | 1298% |
| June 2026 | Chloride [as Cl], daily maximum | 5017 | ≤ 390 mg/L | 1186% |
| June 2026 | Chloride [as Cl], monthly average | 5017 | ≤ 390 mg/L | 1186% |
| July 2026 | Chloride [as Cl], daily maximum | 5081 | ≤ 390 mg/L | 1203% |
| July 2026 | Chloride [as Cl], monthly average | 5081 | ≤ 390 mg/L | 1203% |
| August 2026 | Chloride [as Cl], daily maximum | 5136 | ≤ 390 mg/L | 1217% |
| August 2026 | Chloride [as Cl], monthly average | 5136 | ≤ 390 mg/L | 1217% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | minimum | ≥ 5 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | monthly average | ≤ 30 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 60 mg/L | all year |
| Chloride [as Cl] | monthly average | ≤ 390 mg/L | all year |
| Chloride [as Cl] | daily maximum | ≤ 390 mg/L | all year |
| Flow, in conduit or thru treatment plant | monthly average | report only (MGD) | all year |
| Flow, in conduit or thru treatment plant | maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly average | ≤ .016 mg/L | all year |
| Chlorine, total residual | daily maximum | ≤ .016 mg/L | all year |
| TU Static Renewal 7-Day Chronic Ceriodaphnia dubia | maximum | ≤ 7.14 tox chronic | all year |
| Parameter | New limit | New or tighter | Median, last 12 months | × new limit |
|---|---|---|---|---|
| Chloride [as Cl], monthly average | 360 mg/L | tighter | 5017 mg/L (11 values) | 13.9× |
Cited limits by parameter: Virginia's rules and the federal ones.
Same industry: the 24 Water Supply permits in Virginia.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/VA0078778 · MCP: https://passage-data.com/mcp