Passage Data · Check a report · Use it from your AI

Appalachian Power Company

Electric Services, major discharger, Cleveland, Virginia. NPDES permit VA0001015, in force until Nov 30, 2030. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 10 days after each period: outfall 003 form M1 monthly (12 values), outfall 007 form M1 monthly (5 values), outfall 008 form M1 monthly (5 values), outfall 750 form M1 monthly (4 values), outfall 003 form A1 yearly, outfall 003 form Q1 quarterly, and 6 more forms
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 66 reports late

Limits in force (61)

ParameterStatisticLimitMonthsOutfall
pHdaily minimum≥ 6 SUall year003
pHdaily maximum≤ 9 SUall year003
Solids, total suspendedmonthly average≤ 30 mg/Lall year003
Solids, total suspendeddaily maximum≤ 100 mg/Lall year003
Oil & Greasemonthly average≤ 15 mg/Lall year003
Oil & Greasemaximum≤ 20 mg/Lall year003
Nitrogen, ammonia total [as N]monthly average≤ 2.9 mg/Lall year003
Nitrogen, ammonia total [as N]daily maximum≤ 2.9 mg/Lall year003
Iron, total recoverablemonthly average≤ 1 mg/Lall year003
Iron, total recoverabledaily maximum≤ 1 mg/Lall year003
Selenium, total recoverablemonthly average≤ 17.3 ug/Lall year003
Selenium, total recoverabledaily maximum≤ 17.3 ug/Lall year003
Zinc, total recoverablemonthly average≤ 1 mg/Lall year003
Zinc, total recoverablemaximum≤ 1 mg/Lall year003
Chromium, total recoverablemonthly average≤ .2 mg/Lall year003
Chromium, total recoverablemaximum≤ .2 mg/Lall year003
Copper, total recoverablemonthly average≤ 37 ug/Lall year003
Copper, total recoverabledaily maximum≤ 37 ug/Lall year003
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year003
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year003
Chlorine, total residualmonthly average≤ 40 ug/Lall year003
Chlorine, total residualinstantaneous maximum≤ 40 ug/Lall year003
pHminimum≥ 6 SUall year007
pHmaximum≤ 9 SUall year007
Solids, total suspendeddaily maximum≤ 50 mg/Lall year007
Oil & Greasedaily maximumreport only (mg/L)all year007
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year007
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year007
BOD, 5-day, 20 deg. Cmonthly average≤ 30 mg/Lall year008
BOD, 5-day, 20 deg. Cweekly average≤ 45 mg/Lall year008
BOD, 5-day, 20 deg. Cmonthly average≤ 1.4 kg/dall year008
BOD, 5-day, 20 deg. Cweekly average≤ 2 kg/dall year008
BOD, 5-day, 20 deg. Cmonthly averagereport only (mg/L)all year008
pHminimum≥ 6 SUall year008
pHmaximum≤ 9 SUall year008
Solids, total suspendedmonthly average≤ 30 mg/Lall year008
Solids, total suspendedweekly average≤ 45 mg/Lall year008
Solids, total suspendedmonthly average≤ 1.4 kg/dall year008
Solids, total suspendedweekly average≤ 2 kg/dall year008
Solids, total suspendedmonthly averagereport only (mg/L)all year008
Flow, in conduit or thru treatment plantmonthly average≤ .012 MGDall year008
Flow, in conduit or thru treatment plantmaximumreport only (MGD)all year008
BOD, percent removal [total]monthly average minimum≥ 85 %all year008
E. coligeometric mean≤ 126 #/100mLall year008
Solids, suspended percent removalmonthly average minimum≥ 85 %all year008
pHminimumreport only (SU)all year015
pHmaximumreport only (SU)all year015
Solids, total suspendedmaximumreport only (mg/L)all year015
Oil & Greasemaximumreport only (mg/L)all year015
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year015
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year015
pHminimumreport only (SU)all year727
pHmaximumreport only (SU)all year727
Solids, total suspendedmaximumreport only (mg/L)all year727
Oil & Greasemaximumreport only (mg/L)all year727
Iron, total recoverablemaximumreport only (mg/L)all year727
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year727
Flow, in conduit or thru treatment plantmonthly averagereport only (MGD)all year750
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year750
Velocity of intakemonthly averagereport only (ft/sec)all year750
Velocity of intakedaily maximumreport only (ft/sec)all year750

How strict are these limits?

Cited limits by parameter: Virginia's rules and the federal ones.

Same industry: the 24 Electric Services permits in Virginia.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/VA0001015 · MCP: https://passage-data.com/mcp