Water Supply, South Salt Lake, Utah. NPDES permit UT0026395, in force until Jul 31, 2031. No reports in EPA's file for the last 12 months. Source: EPA ECHO, Oct 22, 2026.
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | daily minimum | ≥ 6.5 mg/L | all year |
| pH | daily minimum | ≥ 6.5 SU | all year |
| pH | daily maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily maximum | ≤ 90 mg/L | all year |
| Oil & Grease | daily maximum | ≤ 10 mg/L | all year |
| Phosphorus, total [as P] | 30-day average | report only (mg/L) | all year |
| Phosphorus, total [as P] | annual average | ≤ 1 mg/L | all year |
| Cyanide, total [as CN] | daily maximum | report only (mg/L) | all year |
| Arsenic, total [as As] | daily maximum | report only (mg/L) | all year |
| Cadmium, total [as Cd] | daily maximum | report only (mg/L) | all year |
| Chromium, total [as Cr] | daily maximum | report only (mg/L) | all year |
| Copper, total [as Cu] | daily maximum | report only (mg/L) | all year |
| Lead, total [as Pb] | daily maximum | report only (mg/L) | all year |
| Molybdenum, total [as Mo] | daily maximum | report only (mg/L) | all year |
| Nickel, total [as Ni] | daily maximum | report only (mg/L) | all year |
| Silver, total [as Ag] | daily maximum | report only (mg/L) | all year |
| Zinc, total [as Zn] | daily maximum | report only (mg/L) | all year |
| Selenium, total [as Se] | daily maximum | report only (mg/L) | all year |
| Chlorine, total residual | daily maximum | ≤ .04 mg/L | Apr–Dec |
| Chlorine, total residual | daily maximum | ≤ .03 mg/L | Jan–Mar |
| Solids, total dissolved | 30-day average | report only (mg/L) | all year |
| Solids, total dissolved | daily maximum | report only (mg/L) | all year |
| Mercury, total [as Hg] | daily maximum | report only (mg/L) | all year |
| Organics, total toxic [TTO] | daily maximum | report only (mg/L) | all year |
| Flow, total | daily maximum | ≤ 72000 gal/d | all year |
Cited limits by parameter: Utah's rules and the federal ones.
Same industry: the 11 Water Supply permits in Utah.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/UT0026395 · MCP: https://passage-data.com/mcp