Passage Data · Check a report · Use it from your AI
Natural Gas Liquids, Baytown, Texas. NPDES permit TX0147265, in force until Feb 12, 2031. Last 12 months: over a limit 2 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Carbon, tot organic [TOC], daily maximum | 81.4 mg/L | ≤ 75 mg/L | 9% |
| June 2026 | pH, maximum | 9.5 SU | ≤ 9 SU | — |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Solids, total suspended | daily maximum | report only (mg/L) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | ≤ 2.88 MGD | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 6.6 MGD | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | maximum | ≤ 9 SU | all year | 002 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 002 |
| Carbon, tot organic [TOC] | daily maximum | ≤ 75 mg/L | all year | 002 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 002 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 002 |
| pH | minimum | ≥ 6 SU | all year | 003 |
| pH | maximum | ≤ 9 SU | all year | 003 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 003 |
| Carbon, tot organic [TOC] | daily maximum | ≤ 75 mg/L | all year | 003 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 003 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 003 |
| pH | minimum | ≥ 6 SU | all year | 004 |
| pH | maximum | ≤ 9 SU | all year | 004 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 004 |
| Carbon, tot organic [TOC] | daily maximum | ≤ 75 mg/L | all year | 004 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 004 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 004 |
| pH | minimum | ≥ 6 SU | all year | 005 |
| pH | maximum | ≤ 9 SU | all year | 005 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 005 |
| Carbon, tot organic [TOC] | daily maximum | ≤ 75 mg/L | all year | 005 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 005 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 005 |
| pH | minimum | ≥ 6 SU | all year | 006 |
| pH | maximum | ≤ 9 SU | all year | 006 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 006 |
| Carbon, tot organic [TOC] | daily maximum | ≤ 75 mg/L | all year | 006 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 006 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 006 |
Cited limits by parameter: Texas's rules and the federal ones.
Same industry: the 30 Oil and Gas Extraction permits in Texas.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0147265 · MCP: https://passage-data.com/mcp