Sewerage Systems, Plantersville, Texas. NPDES permit TX0141852, in force until Sep 8, 2031. Last 12 months: over a limit 5 times (last July 2026), 2 required values missing, 4 of 13 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Nitrogen, ammonia total [as N], single grab sample | 20.6 mg/L | ≤ 15 mg/L | 37% |
| February 2026 | E. coli, daily average | 95 MPN/100mL | ≤ 63 MPN/100mL | 51% |
| June 2026 | Flow, in conduit or thru treatment plant, daily average | 101121 MGD | ≤ .12 MGD | — |
| July 2026 | BOD, carbonaceous [5 day, 20 C], daily average | 11.5 mg/L | ≤ 10 mg/L | 15% |
| July 2026 | BOD, carbonaceous [5 day, 20 C], daily maximum | 40 mg/L | ≤ 35 mg/L | 14% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 15 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 3 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 3 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .12 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 63 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 200 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily maximum | ≤ 35 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.