Passage Data · Check a report · Use it from your AI

Aqua Texas Inc

Sewerage Systems, City Of Elmendorf, Texas. NPDES permit TX0140996 expired Oct 22, 2026. Last 12 months: over a limit 8 times (last August 2026), 11 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (16 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
2 values over a limit, 20 required values missing, 10 of 11 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
April 2026Flow, in conduit or thru treatment plant, daily average.0308 MGD≤ .03 MGD3%
May 2026Flow, in conduit or thru treatment plant, daily average.0328 MGD≤ .03 MGD9%
June 2026Flow, in conduit or thru treatment plant, daily average.035 MGD≤ .03 MGD17%
June 2026Oxygen, dissolved [DO], monthly minimum5.65 mg/L≥ 6 mg/L6%
July 2026E. coli, single grab sample> 2420 CFU/100mL≤ 200 CFU/100mL—
July 2026Flow, in conduit or thru treatment plant, daily average.039 MGD≤ .03 MGD30%
August 2026Flow, in conduit or thru treatment plant, daily average.044≤ .03 MGD47%
August 2026Oxygen, dissolved [DO], monthly minimum1.27≥ 6 mg/L79%

Limits in force (19)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 6 mg/Lall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 15 mg/Lall year
Solids, total suspendedsingle grab sample≤ 60 mg/Lall year
Solids, total suspendeddaily average≤ 3.8 lb/dall year
Nitrogen, ammonia total [as N]daily average≤ 3 mg/Lall year
Nitrogen, ammonia total [as N]single grab sample≤ 15 mg/Lall year
Nitrogen, ammonia total [as N]daily average≤ .75 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .03 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
E. colidaily average≤ 63 CFU/100mLall year
E. colisingle grab sample≤ 200 CFU/100mLall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 10 mg/Lall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 10 mg/Lall year
BOD, carbonaceous [5 day, 20 C]single grab sample≤ 35 mg/Lall year
BOD, carbonaceous [5 day, 20 C]single grab sample≤ 35 mg/Lall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 21 lb/dall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 2.5 lb/dall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0140996 · MCP: https://passage-data.com/mcp