Passage Data · Check a report · Use it from your AI

Texas RV Ranch, LLC

Sewerage Systems, Alvarado, Texas. NPDES permit TX0137987, in force until Jul 17, 2028. Last 12 months: over a limit 24 times (last August 2026), 2 required values missing. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (13 values), form Q quarterly
Renewal application due
Jan 19, 2028 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
27 values over a limit, 0 required values missing, 2 of 16 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

All 24 values over a limit
Period endingParameterReportedLimitOver by
October 2025BOD, 5-day, 20 deg. C, daily average110.6 mg/L≤ 20 mg/L453%
October 2025BOD, 5-day, 20 deg. C, single grab sample142 mg/L≤ 65 mg/L118%
October 2025E. coli, daily average1046 CFU/100mL≤ 126 CFU/100mL730%
October 2025E. coli, single grab sample1046 CFU/100mL≤ 399 CFU/100mL162%
October 2025Solids, total suspended, daily average33.6 mg/L≤ 20 mg/L68%
November 2025BOD, 5-day, 20 deg. C, daily average89.75 mg/L≤ 20 mg/L349%
November 2025BOD, 5-day, 20 deg. C, single grab sample124 mg/L≤ 65 mg/L91%
November 2025Solids, total suspended, daily average24.75 mg/L≤ 20 mg/L24%
December 2025BOD, 5-day, 20 deg. C, daily average43.33 mg/L≤ 20 mg/L117%
February 2026BOD, 5-day, 20 deg. C, daily average27 mg/L≤ 20 mg/L35%
April 2026BOD, 5-day, 20 deg. C, daily average35.6 mg/L≤ 20 mg/L78%
April 2026BOD, 5-day, 20 deg. C, single grab sample91 mg/L≤ 65 mg/L40%
April 2026Solids, total suspended, daily average34.6 mg/L≤ 20 mg/L73%
April 2026Solids, total suspended, single grab sample80 mg/L≤ 65 mg/L23%
May 2026BOD, 5-day, 20 deg. C, daily average30.5 mg/L≤ 20 mg/L53%
May 2026Solids, total suspended, daily average24.25 mg/L≤ 20 mg/L21%
June 2026BOD, 5-day, 20 deg. C, daily average33.6 mg/L≤ 20 mg/L68%
June 2026BOD, 5-day, 20 deg. C, single grab sample73 mg/L≤ 65 mg/L12%
June 2026Solids, total suspended, daily average27.8 mg/L≤ 20 mg/L39%
July 2026BOD, 5-day, 20 deg. C, daily average35.25 mg/L≤ 20 mg/L76%
July 2026BOD, 5-day, 20 deg. C, single grab sample97 mg/L≤ 65 mg/L49%
July 2026Solids, total suspended, daily average33.25 mg/L≤ 20 mg/L66%
July 2026Solids, total suspended, single grab sample104 mg/L≤ 65 mg/L60%
August 2026BOD, 5-day, 20 deg. C, daily average25 mg/L≤ 20 mg/L25%

Limits in force (15)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 2 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 20 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 65 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 5 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 20 mg/Lall year
Solids, total suspendedsingle grab sample≤ 65 mg/Lall year
Solids, total suspendeddaily average≤ 5 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .03 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0137987 · MCP: https://passage-data.com/mcp