Passage Data · Check a report · Use it from your AI
Sewerage Systems, Colorado County, Texas. NPDES permit TX0137634, in force until Aug 26, 2030. Last 12 months: over a limit 15 times (last September 2026), 1 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | E. coli, single grab sample | 1990 MPN/100mL | ≤ 399 CFU/100mL | 399% |
| November 2025 | E. coli, single grab sample | 1730 MPN/100mL | ≤ 399 CFU/100mL | 334% |
| November 2025 | Oxygen, dissolved [DO], monthly minimum | .4 mg/L | ≥ 4 mg/L | 90% |
| December 2025 | E. coli, single grab sample | 12000 MPN/100mL | ≤ 399 CFU/100mL | 2908% |
| February 2026 | Oxygen, dissolved [DO], monthly minimum | 1.45 mg/L | ≥ 4 mg/L | 64% |
| March 2026 | Oxygen, dissolved [DO], monthly minimum | 2.13 mg/L | ≥ 4 mg/L | 47% |
| March 2026 | Solids, total suspended, daily average | 39.2 mg/L | ≤ 15 mg/L | 161% |
| March 2026 | Solids, total suspended, single grab sample | 151.9 mg/L | ≤ 60 mg/L | 153% |
| May 2026 | E. coli, single grab sample | 2420 MPN/100mL | ≤ 399 CFU/100mL | 507% |
| May 2026 | Solids, total suspended, daily average | 42.05 mg/L | ≤ 15 mg/L | 180% |
| May 2026 | Solids, total suspended, single grab sample | 84 mg/L | ≤ 60 mg/L | 40% |
| June 2026 | E. coli, single grab sample | 8160 MPN/100mL | ≤ 399 CFU/100mL | 1945% |
| July 2026 | E. coli, single grab sample | 410 MPN/100mL | ≤ 399 CFU/100mL | 3% |
| August 2026 | E. coli, single grab sample | 1400 MPN/100mL | ≤ 399 CFU/100mL | 251% |
| September 2026 | E. coli, single grab sample | 1050 MPN/100mL | ≤ 399 CFU/100mL | 163% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 3 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 3 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ .6 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .025 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | single grab sample | ≤ 35 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 2 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0137634 · MCP: https://passage-data.com/mcp