Electric Services, major discharger, Gregory, Texas. NPDES permit TX0137502, in force until May 26, 2031. Last 12 months: over a limit 2 times (last September 2026), 1 required value missing, 3 of 47 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Outfall | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|---|
| March 2026 | 201 | Solids, total suspended, daily average | 41 mg/L | ≤ 30 mg/L | 37% |
| September 2026 | 101 | Flow, in conduit or thru treatment plant, daily maximum | 1.13 MGD | ≤ .999 MGD | 13% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. fahrenheit | daily average | report only (deg F) | all year | 001 |
| Temperature, water deg. fahrenheit | daily maximum | report only (deg F) | all year | 001 |
| Copper, total [as Cu] | daily maximum | report only (mg/L) | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | ≤ .918 MGD | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 2.11 MGD | all year | 001 |
| Chlorine, total residual | daily maximum | ≤ .1 mg/L | all year | 001 |
| pH | minimum | ≥ 6.5 SU | all year | 101 |
| pH | maximum | ≤ 9 SU | all year | 101 |
| Chromium, total [as Cr] | daily average | ≤ .2 mg/L | all year | 101 |
| Chromium, total [as Cr] | daily maximum | ≤ .2 mg/L | all year | 101 |
| Chromium, total [as Cr] | daily average | ≤ 1.38 lb/d | all year | 101 |
| Chromium, total [as Cr] | daily maximum | ≤ 1.38 lb/d | all year | 101 |
| Zinc, total [as Zn] | daily average | ≤ 1 mg/L | all year | 101 |
| Zinc, total [as Zn] | daily maximum | ≤ 1 mg/L | all year | 101 |
| Zinc, total [as Zn] | daily average | ≤ 6.94 lb/d | all year | 101 |
| Zinc, total [as Zn] | daily maximum | ≤ 6.94 lb/d | all year | 101 |
| Flow, in conduit or thru treatment plant | daily average | ≤ .832 MGD | all year | 101 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .999 MGD | all year | 101 |
| pH | minimum | ≥ 6.5 SU | all year | 201 |
| pH | maximum | ≤ 9 SU | all year | 201 |
| Solids, total suspended | daily average | ≤ 30 mg/L | all year | 201 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 201 |
| Solids, total suspended | daily average | ≤ 21.2 lb/d | all year | 201 |
| Solids, total suspended | daily maximum | ≤ 70.9 lb/d | all year | 201 |
| Oil & Grease | daily average | ≤ 15 mg/L | all year | 201 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 201 |
| Oil & Grease | daily average | ≤ 10.6 lb/d | all year | 201 |
| Oil & Grease | daily maximum | ≤ 14.1 lb/d | all year | 201 |
| Flow, in conduit or thru treatment plant | daily average | ≤ .085 MGD | all year | 201 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ 1.105 MGD | all year | 201 |
| Parameter | New limit | New or tighter | Median, last 12 months | × new limit |
|---|---|---|---|---|
| Copper, total [as Cu], daily average | 0.0064 mg/L | new | — | — |
| Copper, total [as Cu], daily average | 0.049 lb/d | new | — | — |
| Copper, total [as Cu], daily maximum | 0.103 lb/d | new | — | — |
| Copper, total [as Cu], daily maximum | 0.0135 mg/L | new | 0.01 mg/L (12 values) | 0.741× |
Cited limits by parameter: Texas's rules and the federal ones.
Same industry: the 87 Electric Services permits in Texas.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0137502 · MCP: https://passage-data.com/mcp