Windy Hill Utility Co LLC

Sewerage Systems, Kyle, Texas. NPDES permit TX0137111, in force until Dec 31, 2030. Last 12 months: over a limit 5 times (last April 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (21 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
2 values over a limit, 0 required values missing, 0 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
November 2025Flow, in conduit or thru treatment plant, daily average.13 MGD≤ .12 MGD8%
January 2026Flow, in conduit or thru treatment plant, daily average.13 MGD≤ .12 MGD8%
January 2026Nitrogen, ammonia total [as N], daily average5 lb/d≤ 2 lb/d150%
January 2026Nitrogen, ammonia total [as N], daily average5 mg/L≤ 2 mg/L150%
April 2026Flow, in conduit or thru treatment plant, daily average.13 MGD≤ .12 MGD8%

Limits in force (21)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 5 mg/Lall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 5 mg/Lall year
Solids, total suspendedsingle grab sample≤ 30 mg/Lall year
Solids, total suspendeddaily average≤ 11 lb/dall year
Nitrogen, ammonia total [as N]daily average≤ 2 mg/Lall year
Nitrogen, ammonia total [as N]single grab sample≤ 15 mg/Lall year
Nitrogen, ammonia total [as N]daily average≤ 4.3 lb/dall year
Phosphorus, total [as P]daily average≤ 1 mg/Lall year
Phosphorus, total [as P]single grab sample≤ 6 mg/Lall year
Phosphorus, total [as P]daily average≤ 2.2 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .26 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colidaily maximum≤ 399 CFU/100mLall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 5 mg/Lall year
BOD, carbonaceous [5 day, 20 C]single grab sample≤ 30 mg/Lall year
BOD, carbonaceous [5 day, 20 C]daily average≤ 11 lb/dall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history