Passage Data · Check a report · Use it from your AI
Sewage treatment plant, City Of Deport, Texas. NPDES permit TX0136930 expired Sep 23, 2026; its limits still apply. Last 12 months: over a limit 11 times (last September 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | E. coli, daily average | 265 CFU/100mL | ≤ 126 CFU/100mL | 110% |
| December 2025 | E. coli, single grab sample | 411 CFU/100mL | ≤ 399 CFU/100mL | 3% |
| January 2026 | E. coli, daily average | 273 CFU/100mL | ≤ 126 CFU/100mL | 117% |
| January 2026 | E. coli, single grab sample | 435 CFU/100mL | ≤ 399 CFU/100mL | 9% |
| March 2026 | E. coli, daily average | 129 CFU/100mL | ≤ 126 CFU/100mL | 2% |
| May 2026 | E. coli, daily average | 319 CFU/100mL | ≤ 126 CFU/100mL | 153% |
| May 2026 | E. coli, single grab sample | 613 CFU/100mL | ≤ 399 CFU/100mL | 54% |
| June 2026 | E. coli, daily average | 897 CFU/100mL | ≤ 126 CFU/100mL | 612% |
| June 2026 | E. coli, single grab sample | 1730 CFU/100mL | ≤ 399 CFU/100mL | 334% |
| September 2026 | E. coli, daily average | 308 CFU/100mL | ≤ 126 CFU/100mL | 144% |
| September 2026 | E. coli, single grab sample | 488 CFU/100mL | ≤ 399 CFU/100mL | 22% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 46 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 137 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .183 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0136930 · MCP: https://passage-data.com/mcp