Passage Data · Check a report · Use it from your AI
Sewerage Systems, Richmond, Texas. NPDES permit TX0136913, in force until Feb 3, 2027. Last 12 months: over a limit 10 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | Oxygen, dissolved [DO], monthly minimum | 2.9 mg/L | ≥ 4 mg/L | 28% |
| June 2026 | BOD, 5-day, 20 deg. C, daily average | 13.2 mg/L | ≤ 10 mg/L | 32% |
| June 2026 | Oxygen, dissolved [DO], monthly minimum | 3.5 mg/L | ≥ 4 mg/L | 13% |
| June 2026 | Solids, total suspended, daily average | 21.875 mg/L | ≤ 15 mg/L | 46% |
| June 2026 | Solids, total suspended, daily average | 7.844 lb/d | ≤ 7.8 lb/d | 1% |
| July 2026 | Oxygen, dissolved [DO], monthly minimum | 3.8 mg/L | ≥ 4 mg/L | 5% |
| July 2026 | Solids, total suspended, daily average | 16.2 lb/d | ≤ 7.8 lb/d | 108% |
| July 2026 | Solids, total suspended, daily average | 45.4 mg/L | ≤ 15 mg/L | 203% |
| July 2026 | Solids, total suspended, single grab sample | 149 mg/L | ≤ 60 mg/L | 148% |
| August 2026 | E. coli, single grab sample | 1553.1 CFU/100mL | ≤ 399 CFU/100mL | 289% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 10 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 35 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 5.2 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 7.8 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .0625 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0136913 · MCP: https://passage-data.com/mcp