Passage Data · Check a report · Use it from your AI
Sewerage Systems, New Caney, Texas. NPDES permit TX0136867, in force until Aug 28, 2029. Last 12 months: over a limit 11 times (last January 2026), 18 required values missing, 2 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Solids, total suspended, daily average | 6.5 lb/d | ≤ 5 lb/d | 30% |
| November 2025 | Solids, total suspended, daily average | 62 mg/L | ≤ 15 mg/L | 313% |
| November 2025 | Solids, total suspended, single grab sample | 234 mg/L | ≤ 60 mg/L | 290% |
| December 2025 | Flow, in conduit or thru treatment plant, daily average | .457 MGD | ≤ .04 MGD | 1043% |
| December 2025 | Nitrogen, ammonia total [as N], daily average | 3.88 mg/L | ≤ 3 mg/L | 29% |
| January 2026 | Flow, in conduit or thru treatment plant, daily average | 1.621 MGD | ≤ .04 MGD | 3953% |
| January 2026 | Flow, in conduit or thru treatment plant, daily average | 1.621 MGD | ≤ .04 MGD | 3953% |
| January 2026 | Nitrogen, ammonia total [as N], daily average | 46.6 mg/L | ≤ 3 mg/L | 1453% |
| January 2026 | Nitrogen, ammonia total [as N], daily average | 46.6 mg/L | ≤ 3 mg/L | 1453% |
| January 2026 | Nitrogen, ammonia total [as N], single grab sample | 47 mg/L | ≤ 15 mg/L | 213% |
| January 2026 | Nitrogen, ammonia total [as N], single grab sample | 47 mg/L | ≤ 15 mg/L | 213% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 5 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 3 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 1 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .04 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 63 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 200 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | single grab sample | ≤ 35 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 3.3 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.