Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Anthony, Texas. NPDES permit TX0136662 expired Dec 16, 2025; its limits still apply. Last 12 months: over a limit 9 times (last September 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| May 2026 | BOD, 5-day, 20 deg. C, daily average | 21.23 mg/L | ≤ 20 mg/L | 6% |
| June 2026 | Solids, total suspended, daily average | 30.08 mg/L | ≤ 20 mg/L | 50% |
| June 2026 | Solids, total suspended, daily maximum | 58 mg/L | ≤ 45 mg/L | 29% |
| July 2026 | Solids, total suspended, daily average | 27.78 mg/L | ≤ 20 mg/L | 39% |
| July 2026 | Solids, total suspended, daily maximum | 54 mg/L | ≤ 45 mg/L | 20% |
| August 2026 | Solids, total suspended, daily average | 22.79 mg/L | ≤ 20 mg/L | 14% |
| August 2026 | Solids, total suspended, daily maximum | 46.7 mg/L | ≤ 45 mg/L | 4% |
| September 2026 | Solids, total suspended, daily maximum | 50 mg/L | ≤ 45 mg/L | 11% |
| September 2026 | pH, maximum | 10 SU | ≤ 9 SU | — |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily maximum | ≤ 45 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 94 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 45 mg/L | all year |
| Solids, total suspended | daily average | ≤ 94 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .565 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | daily maximum | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0136662 · MCP: https://passage-data.com/mcp