Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Richmond, Texas. NPDES permit TX0135259, in force until Aug 12, 2027. Last 12 months: over a limit 6 times (last February 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| January 2026 | Nitrogen, ammonia total [as N], daily average | 2.34 mg/L | ≤ 2 mg/L | 17% |
| January 2026 | Solids, total suspended, daily average | 41.68 mg/L | ≤ 15 mg/L | 178% |
| January 2026 | Solids, total suspended, daily maximum | 98 mg/L | ≤ 40 mg/L | 145% |
| February 2026 | Solids, total suspended, daily average | 114.1 lb/d | ≤ 75 lb/d | 52% |
| February 2026 | Solids, total suspended, daily average | 81.48 mg/L | ≤ 15 mg/L | 443% |
| February 2026 | Solids, total suspended, daily maximum | 140 mg/L | ≤ 40 mg/L | 250% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 6 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 40 mg/L | all year |
| Solids, total suspended | daily average | ≤ 113 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 2 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 10 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 15 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .9 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 63 CFU/100mL | all year |
| E. coli | daily maximum | ≤ 200 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 10 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily maximum | ≤ 25 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 75 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0135259 · MCP: https://passage-data.com/mcp