Passage Data · Check a report

MONTGOMERY COUNTY MUNICIPAL UTILITY DISTRICT 123

NPDES permit TX0129585 · EPA data of Oct 12, 2026

What it is
Industrial or other facility
Where
Texas · map
Last 12 months
No reports in EPA's file
Permit
In force until Feb 9, 2028

What brings you here? · ·

Check this month's numbers before you file
Email me before each report is due. Free. Reply to any email to stop.
Renewal check Free while we pilot it.

Renewal application due Aug 13, 2027. What the next permit may change: each limit a renewal could tighten or add, from Texas's water-quality standards and the federal rules for this kind of discharge, each cited to its rule, beside EPA's 12-month record. A rule we do not hold is named, never guessed. By email within 5 business days.

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

EPA has no reports on file for this permit in this window. That may be EPA's gap, not the facility's.

Reporting

Reports due
About 20 days after each period ends

How strict are these limits?

Compared with the same limit in similar permits.

Limits in force (18)

OutfallParameterStatisticLimitMonths
001Oxygen, dissolved [DO]monthly minimum >= 4 mg/L all year
001pHminimum >= 6 SU all year
001pHmaximum <= 9 SU all year
001Solids, total suspendeddaily average <= 15 mg/L all year
001Solids, total suspendedsingle grab sample <= 60 mg/L all year
001Solids, total suspendeddaily average <= 25 lb/d all year
001Nitrogen, ammonia total [as N]daily average <= 3 mg/L all year
001Nitrogen, ammonia total [as N]single grab sample <= 15 mg/L all year
001Nitrogen, ammonia total [as N]daily average <= 5 lb/d all year
001Flow, in conduit or thru treatment plantdaily average <= .2 MGD all year
001Flow, in conduit or thru treatment plantdaily maximum report only all year
001Chlorine, total residualmonthly minimum >= 1 mg/L all year
001Chlorine, total residualmonthly maximum <= 4 mg/L all year
001E. colidaily average <= 63 CFU/100mL all year
001E. colisingle grab sample <= 200 CFU/100mL all year
001BOD, carbonaceous [5 day, 20 C]daily average <= 10 mg/L all year
001BOD, carbonaceous [5 day, 20 C]single grab sample <= 35 mg/L all year
001BOD, carbonaceous [5 day, 20 C]daily average <= 17 lb/d all year

Cited limits by parameter: Texas's rules and the federal ones, each row cited to the rule it comes from.