Sewage treatment plant, Waller, Texas. NPDES permit TX0127264, in force until Jun 9, 2027. Last 12 months: over a limit 14 times (last May 2026), 1 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Solids, total suspended, daily average | 26.9 mg/L | ≤ 15 mg/L | 79% |
| November 2025 | BOD, carbonaceous [5 day, 20 C], daily average | 6.62 mg/L | ≤ 5 mg/L | 32% |
| November 2025 | Solids, total suspended, daily average | 23.5 mg/L | ≤ 15 mg/L | 57% |
| December 2025 | BOD, carbonaceous [5 day, 20 C], daily average | 6.7 mg/L | ≤ 5 mg/L | 34% |
| December 2025 | Nitrogen, ammonia total [as N], daily average | 7.06 mg/L | ≤ 2 mg/L | 253% |
| December 2025 | Nitrogen, ammonia total [as N], single grab sample | 19.8 mg/L | ≤ 15 mg/L | 32% |
| December 2025 | Solids, total suspended, daily average | 41.61 lb/d | ≤ 39 lb/d | 7% |
| December 2025 | Solids, total suspended, daily average | 64.8 mg/L | ≤ 15 mg/L | 332% |
| December 2025 | Solids, total suspended, single grab sample | 162 mg/L | ≤ 60 mg/L | 170% |
| January 2026 | Solids, total suspended, daily average | 17.4 mg/L | ≤ 15 mg/L | 16% |
| February 2026 | BOD, carbonaceous [5 day, 20 C], daily average | 6.18 mg/L | ≤ 5 mg/L | 24% |
| February 2026 | Solids, total suspended, daily average | 28.7 mg/L | ≤ 15 mg/L | 91% |
| May 2026 | E. coli, daily average | 260 CFU/100mL | ≤ 63 CFU/100mL | 313% |
| May 2026 | E. coli, single grab sample | 260 CFU/100mL | ≤ 200 CFU/100mL | 30% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 6 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 60 mg/L | all year |
| Solids, total suspended | daily average | ≤ 39 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 2 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 5.2 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .31 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 63 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 200 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 5 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | single grab sample | ≤ 30 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 13 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.