Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Realitos Colonia, Texas. NPDES permit TX0127141, in force until Mar 9, 2031. Last 12 months: over a limit 10 times (last June 2026), 2 required values missing, 1 of 15 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | Flow, in conduit or thru treatment plant, daily average | .076112 MGD | ≤ .04 MGD | 90% |
| November 2025 | Flow, in conduit or thru treatment plant, daily average | .079494 MGD | ≤ .04 MGD | 99% |
| December 2025 | Flow, in conduit or thru treatment plant, daily average | .083373 MGD | ≤ .04 MGD | 108% |
| January 2026 | Flow, in conduit or thru treatment plant, daily average | .085741 MGD | ≤ .04 MGD | 114% |
| February 2026 | Flow, in conduit or thru treatment plant, daily average | .087575 MGD | ≤ .04 MGD | 119% |
| March 2026 | Flow, in conduit or thru treatment plant, daily average | .08881 MGD | ≤ .04 MGD | 122% |
| March 2026 | pH, maximum | 9.06 SU | ≤ 9 SU | — |
| April 2026 | Flow, in conduit or thru treatment plant, daily average | .091199 MGD | ≤ .04 MGD | 128% |
| May 2026 | Flow, in conduit or thru treatment plant, daily average | .094519 MGD | ≤ .04 MGD | 136% |
| June 2026 | Flow, in conduit or thru treatment plant, daily average | .060004 MGD | ≤ .04 MGD | 50% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 6.7 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 6.7 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .04 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0127141 · MCP: https://passage-data.com/mcp