Sewage treatment plant, Odem, Texas. NPDES permit TX0126641, in force until Jun 19, 2030. Last 12 months: over a limit 10 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | E. coli, single grab sample | 670 CFU/100mL | ≤ 399 CFU/100mL | 68% |
| January 2026 | E. coli, single grab sample | 400 CFU/100mL | ≤ 399 CFU/100mL | 0% |
| April 2026 | E. coli, single grab sample | 1000 CFU/100mL | ≤ 399 CFU/100mL | 151% |
| May 2026 | E. coli, single grab sample | 1000 CFU/100mL | ≤ 399 CFU/100mL | 151% |
| May 2026 | Nitrogen, ammonia total [as N], daily average | 8.655 mg/L | ≤ 4 mg/L | 116% |
| May 2026 | Nitrogen, ammonia total [as N], single grab sample | 25.75 mg/L | ≤ 15 mg/L | 72% |
| June 2026 | E. coli, daily average | 835.2 CFU/100mL | ≤ 126 CFU/100mL | 563% |
| June 2026 | E. coli, single grab sample | 5000 CFU/100mL | ≤ 399 CFU/100mL | 1153% |
| July 2026 | E. coli, single grab sample | 1040 CFU/100mL | ≤ 399 CFU/100mL | 161% |
| August 2026 | E. coli, single grab sample | 1000 CFU/100mL | ≤ 399 CFU/100mL | 151% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 79 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 4 mg/L | all year |
| Nitrogen, ammonia total [as N] | single grab sample | ≤ 15 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 16 lb/d | all year |
| Zinc, total [as Zn] | daily average | report only (mg/L) | all year |
| Zinc, total [as Zn] | single grab sample | report only (mg/L) | all year |
| Zinc, total [as Zn] | daily average | report only (lb/d) | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .475 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 20 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | single grab sample | ≤ 65 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 79 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.