Austin, City of

Electric Services, Cushing, Texas. NPDES permit TX0124842, in force until Jun 8, 2031. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (11 values), outfall 101 form A monthly (6 values), outfall TX1 form Q quarterly (12 values), outfall TXA form S twice a year
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 29 reports late

Limits in force (31)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitdaily averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximum≤ 90 deg Fall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Flow, in conduit or thru treatment plantdaily average≤ 1.75 MGDall year001
Flow, in conduit or thru treatment plantdaily maximum≤ 2.5 MGDall year001
Chlorine, free availabledaily average≤ .2 mg/Lall year001
Chlorine, free availabledaily maximum≤ .5 mg/Lall year001
Chlorine, free availabledaily average≤ .243 lb/dall year001
Chlorine, free availabledaily maximum≤ .608 lb/dall year001
Solids, total dissolveddaily maximumreport only (mg/L)all year001
Solids, total suspendeddaily average≤ 30 mg/Lall year101
Solids, total suspendeddaily maximum≤ 100 mg/Lall year101
Oil & Greasedaily average≤ 15 mg/Lall year101
Oil & Greasedaily maximum≤ 20 mg/Lall year101
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year101
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year101
Whole effluent toxicity - retest #148-hour minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #248-hour minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all yearTX1
IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia magna48-hour minimumreport only (abst=0;prst=1)all yearTX1
IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia magnamonthly average minimumreport only (abst=0;prst=1)all yearTX1
IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (pass=0;fail=1)all yearTX1
IC25 Low Flow Pass/Fail Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
IC25 Lethal Static Renewal 48HR Acute Daphnia magna48-hour minimumreport only (%)all yearTX1
IC25 Lethal Static Renewal 48HR Acute Daphnia magnamonthly average minimumreport only (%)all yearTX1
IC25 Lethal Static Renewal 48HR Acute Pimephales promelas48-hour minimumreport only (%)all yearTX1
IC25 Lethal Static Renewal 48HR Acute Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Daphnia magna survival 24 Hr Acute WETsingle samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXA

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Same industry: the 87 Electric Services permits in Texas.

Check this month's numbers Email me before each report is due