Sewage treatment plant, Evadale, Texas. NPDES permit TX0122564 expired Sep 23, 2026; its limits still apply. Last 12 months: over a limit 16 times (last August 2026), 2 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| October 2025 | E. coli, daily average | 238 CFU/100mL | ≤ 126 CFU/100mL | 89% |
| October 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| November 2025 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| November 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| December 2025 | E. coli, daily average | 204 CFU/100mL | ≤ 126 CFU/100mL | 62% |
| December 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| January 2026 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| January 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| February 2026 | E. coli, daily average | 605 CFU/100mL | ≤ 126 CFU/100mL | 380% |
| February 2026 | E. coli, single grab sample | 921 CFU/100mL | ≤ 399 CFU/100mL | 131% |
| March 2026 | E. coli, single grab sample | 921 CFU/100mL | ≤ 399 CFU/100mL | 131% |
| April 2026 | E. coli, daily average | 303 CFU/100mL | ≤ 126 CFU/100mL | 140% |
| April 2026 | E. coli, single grab sample | 921 CFU/100mL | ≤ 399 CFU/100mL | 131% |
| June 2026 | E. coli, daily average | 867 CFU/100mL | ≤ 126 CFU/100mL | 588% |
| June 2026 | E. coli, single grab sample | 921 CFU/100mL | ≤ 399 CFU/100mL | 131% |
| August 2026 | Oxygen, dissolved [DO], monthly minimum | 2.4 mg/L | ≥ 4 mg/L | 40% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 40 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 120 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .16 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.