Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Sargent, Texas. NPDES permit TX0122483, in force until Nov 6, 2029. Last 12 months: over a limit once (last December 2025), 3 of 12 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | Solids, total suspended, daily average | 21.2 mg/L | ≤ 20 mg/L | 6% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 67 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 67 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .4 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| Enterococci | daily average | ≤ 35 CFU/100mL | all year |
| Enterococci | single grab sample | ≤ 104 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0122483 · MCP: https://passage-data.com/mcp