Passage Data · Check a report · Use it from your AI

Calpine Bosque Energy Center LLC

Electric Services, Clifton, Texas. NPDES permit TX0119890, in force until Mar 22, 2029. Last 12 months: over a limit 2 times (last November 2025). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (9 values), outfall 101 form A monthly (10 values), outfall 201 form A monthly (6 values), outfall 301 form A monthly (6 values), outfall TX1 form S twice a year, outfall TX1 form Y yearly, and 1 more form
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 53 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
November 2025Oxygen demand, chem. [high level] [COD], daily average106.2 mg/L≤ 100 mg/L6%
November 2025Oxygen demand, chem. [high level] [COD], daily maximum376 mg/L≤ 150 mg/L151%

Limits in force (63)

ParameterStatisticLimitMonthsOutfall
Temperature, water deg. fahrenheitdaily averagereport only (deg F)all year001
Temperature, water deg. fahrenheitdaily maximum≤ 102 deg Fall year001
Oxygen demand, chem. [high level] [COD]daily average≤ 100 mg/Lall year001
Oxygen demand, chem. [high level] [COD]daily maximum≤ 150 mg/Lall year001
pHminimum≥ 6.5 SUall year001
pHmaximum≤ 9 SUall year001
Flow, in conduit or thru treatment plantdaily average≤ 5.48 MGDall year001
Flow, in conduit or thru treatment plantdaily maximum≤ 8.23 MGDall year001
Chlorine, total residualdaily maximum≤ .1 mg/Lall year001
Solids, total suspendeddaily average≤ 30 mg/Lall year101
Solids, total suspendeddaily maximum≤ 100 mg/Lall year101
Oil & Greasedaily average≤ 15 mg/Lall year101
Oil & Greasedaily maximum≤ 20 mg/Lall year101
Copper, total [as Cu]daily average≤ 1 mg/Lall year101
Copper, total [as Cu]daily maximum≤ 1 mg/Lall year101
Iron, total [as Fe]daily average≤ 1 mg/Lall year101
Iron, total [as Fe]daily maximum≤ 1 mg/Lall year101
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year101
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year101
Solids, total suspendeddaily average≤ 30 mg/Lall year201
Solids, total suspendeddaily maximum≤ 100 mg/Lall year201
Oil & Greasedaily average≤ 15 mg/Lall year201
Oil & Greasedaily maximum≤ 20 mg/Lall year201
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year201
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year201
Solids, total suspendeddaily average≤ 30 mg/Lall year301
Solids, total suspendeddaily maximum≤ 100 mg/Lall year301
Oil & Greasedaily average≤ 15 mg/Lall year301
Oil & Greasedaily maximum≤ 20 mg/Lall year301
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year301
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year301
Whole effluent toxicity - retest #17-day minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #27-day minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Whole effluent toxicity - retest #1single samplereport only (pass=0;fail=1)all yearTXA
Whole effluent toxicity - retest #2single samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute D. Pulexsingle samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXA

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Same industry: the 87 Electric Services permits in Texas.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0119890 · MCP: https://passage-data.com/mcp