Passage Data · Check a report · Use it from your AI
Sewerage Systems, Navasota, Texas. NPDES permit TX0118656, in force until Feb 23, 2029. Last 12 months: over a limit 4 times (last August 2026), 3 of 15 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| February 2026 | Solids, total suspended, daily average | 20.31 mg/L | ≤ 20 mg/L | 2% |
| February 2026 | Solids, total suspended, single grab sample | 110 mg/L | ≤ 65 mg/L | 69% |
| June 2026 | Solids, total suspended, daily average | 21.6857 mg/L | ≤ 20 mg/L | 8% |
| August 2026 | Solids, total suspended, daily average | 20.56 mg/L | ≤ 20 mg/L | 3% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 2 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 5.6 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 5.6 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .0335 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0118656 · MCP: https://passage-data.com/mcp