Sewage treatment plant, New Summerfield, Texas. NPDES permit TX0107875 expired Jun 14, 2026; its limits still apply. Last 12 months: over a limit 10 times (last September 2026), 4 of 16 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| December 2025 | Chlorine, total residual, monthly minimum | .5 mg/L | ≥ 1 mg/L | 50% |
| December 2025 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| December 2025 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| June 2026 | E. coli, daily average | 2420 CFU/100mL | ≤ 126 CFU/100mL | 1821% |
| June 2026 | E. coli, single grab sample | 2420 CFU/100mL | ≤ 399 CFU/100mL | 507% |
| August 2026 | BOD, 5-day, 20 deg. C, daily average | 45.1 mg/L | ≤ 30 mg/L | 50% |
| August 2026 | Solids, total suspended, daily average | 94.7 mg/L | ≤ 90 mg/L | 5% |
| September 2026 | BOD, 5-day, 20 deg. C, daily average | 36.8 mg/L | ≤ 30 mg/L | 23% |
| September 2026 | E. coli, daily average | 130 CFU/100mL | ≤ 126 CFU/100mL | 3% |
| September 2026 | Solids, total suspended, daily average | 92.1 mg/L | ≤ 90 mg/L | 2% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 4 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 30 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 100 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 15 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 90 mg/L | all year |
| Solids, total suspended | daily average | ≤ 45 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .06 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.