Passage Data · Check a report · Use it from your AI
Electric Services, Brownsville, Texas. NPDES permit TX0105651, in force until Oct 23, 2030. Last 12 months: over a limit once (last June 2026). Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| June 2026 | Solids, total suspended, daily average | 42.5 mg/L | ≤ 30 mg/L | 42% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Temperature, water deg. fahrenheit | daily average | ≤ 115 deg F | all year | 001 |
| Temperature, water deg. fahrenheit | daily maximum | ≤ 120 deg F | all year | 001 |
| pH | minimum | ≥ 6 SU | all year | 001 |
| pH | maximum | ≤ 9 SU | all year | 001 |
| Chloride [as Cl] | daily average | report only (mg/L) | all year | 001 |
| Chloride [as Cl] | daily maximum | report only (mg/L) | all year | 001 |
| Sulfate, total [as SO4] | daily average | ≤ 1750 mg/L | all year | 001 |
| Sulfate, total [as SO4] | daily maximum | ≤ 3710 mg/L | all year | 001 |
| Sulfate, total [as SO4] | daily average | ≤ 1060 lb/d | all year | 001 |
| Sulfate, total [as SO4] | daily maximum | ≤ 2242 lb/d | all year | 001 |
| Copper, total [as Cu] | daily average | ≤ .11 mg/L | all year | 001 |
| Copper, total [as Cu] | daily maximum | ≤ .22 mg/L | all year | 001 |
| Copper, total [as Cu] | daily average | ≤ .34 lb/d | all year | 001 |
| Copper, total [as Cu] | daily maximum | ≤ .68 lb/d | all year | 001 |
| Aluminum, total [as Al] | daily average | ≤ .78 mg/L | all year | 001 |
| Aluminum, total [as Al] | daily maximum | ≤ 1.64 mg/L | all year | 001 |
| Aluminum, total [as Al] | daily average | ≤ 1.66 lb/d | all year | 001 |
| Aluminum, total [as Al] | daily maximum | ≤ 3.51 lb/d | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | ≤ .39 MGD | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .39 MGD | all year | 001 |
| Chlorine, free available | daily average | ≤ .2 mg/L | all year | 001 |
| Chlorine, free available | daily maximum | ≤ .5 mg/L | all year | 001 |
| Chlorine, free available | daily average | ≤ .05 lb/d | all year | 001 |
| Chlorine, free available | daily maximum | ≤ .14 lb/d | all year | 001 |
| Solids, total dissolved | daily average | ≤ 4400 mg/L | all year | 001 |
| Solids, total dissolved | daily maximum | ≤ 9328 mg/L | all year | 001 |
| Solids, total dissolved | daily average | ≤ 13585 lb/d | all year | 001 |
| Solids, total dissolved | daily maximum | ≤ 28801 lb/d | all year | 001 |
| Oxygen demand, chem. [high level] [COD] | daily average | report only (mg/L) | all year | 002 |
| Oxygen demand, chem. [high level] [COD] | daily maximum | ≤ 200 mg/L | all year | 002 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | maximum | ≤ 9 SU | all year | 002 |
| Solids, total suspended | daily average | ≤ 30 mg/L | all year | 002 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 002 |
| Oil & Grease | daily average | ≤ 15 mg/L | all year | 002 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 002 |
| Aluminum, total [as Al] | daily average | report only (mg/L) | all year | 002 |
| Aluminum, total [as Al] | daily maximum | report only (mg/L) | all year | 002 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 002 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 002 |
| Solids, total dissolved | daily average | report only (mg/L) | all year | 002 |
| Solids, total dissolved | daily maximum | report only (mg/L) | all year | 002 |
| pH | minimum | ≥ 6 SU | all year | 102 |
| pH | maximum | ≤ 9 SU | all year | 102 |
| Solids, total suspended | daily average | ≤ 30 mg/L | all year | 102 |
| Solids, total suspended | daily maximum | ≤ 100 mg/L | all year | 102 |
| Oil & Grease | daily average | ≤ 15 mg/L | all year | 102 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 102 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 102 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 102 |
Cited limits by parameter: Texas's rules and the federal ones.
Same industry: the 87 Electric Services permits in Texas.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0105651 · MCP: https://passage-data.com/mcp