Passage Data · Check a report · Use it from your AI

Aqua Texas Inc

Sewerage Systems, Granbury, Texas. NPDES permit TX0098264, in force until Jul 4, 2029. Last 12 months: over a limit 11 times (last August 2026), 2 of 15 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (13 values), form Q quarterly
Last report on file
August 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 0 of 16 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
December 2025Chlorine, total residual, monthly maximum4.12 mg/L≤ 4 mg/L3%
December 2025Solids, total suspended, daily average16.66 mg/L≤ 15 mg/L11%
January 2026Chlorine, total residual, monthly minimum.87 mg/L≥ 1 mg/L13%
January 2026Solids, total suspended, daily average16 mg/L≤ 15 mg/L7%
February 2026Chlorine, total residual, monthly minimum.88 mg/L≥ 1 mg/L12%
March 2026Chlorine, total residual, monthly minimum.88 mg/L≥ 1 mg/L12%
April 2026Chlorine, total residual, monthly minimum.85 mg/L≥ 1 mg/L15%
May 2026Chlorine, total residual, monthly minimum.4 mg/L≥ 1 mg/L60%
June 2026Chlorine, total residual, monthly minimum.26 mg/L≥ 1 mg/L74%
July 2026Chlorine, total residual, monthly minimum.81 mg/L≥ 1 mg/L19%
August 2026Chlorine, total residual, monthly minimum.98 mg/L≥ 1 mg/L2%

Limits in force (15)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 10 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 35 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 7.3 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 15 mg/Lall year
Solids, total suspendedsingle grab sample≤ 60 mg/Lall year
Solids, total suspendeddaily average≤ 11 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .088 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0098264 · MCP: https://passage-data.com/mcp