Passage Data · Check a report · Use it from your AI
Chemical Preparations, Hungerford, Texas. NPDES permit TX0086363, in force until May 20, 2030. Last 12 months: over a limit 2 times (last June 2026), 6 of 24 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| April 2026 | E. coli, daily maximum | 3683 CFU/100mL | ≤ 394 CFU/100mL | 835% |
| June 2026 | E. coli, daily maximum | 998 CFU/100mL | ≤ 394 CFU/100mL | 153% |
| Parameter | Statistic | Limit | Months | Outfall |
|---|---|---|---|---|
| Oxygen demand, chem. [high level] [COD] | daily average | ≤ 100 lb/d | all year | 001 |
| Oxygen demand, chem. [high level] [COD] | daily maximum | ≤ 150 lb/d | all year | 001 |
| pH | minimum | ≥ 5 SU | all year | 001 |
| pH | maximum | ≤ 11 SU | all year | 001 |
| Solids, total suspended | daily average | ≤ 7.9 lb/d | all year | 001 |
| Solids, total suspended | daily maximum | ≤ 11.8 lb/d | all year | 001 |
| Oil & Grease | daily average | ≤ 15 mg/L | all year | 001 |
| Oil & Grease | daily maximum | ≤ 20 mg/L | all year | 001 |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 5 mg/L | all year | 001 |
| Barium, total [as Ba] | daily maximum | ≤ 4 mg/L | all year | 001 |
| Phenols | daily maximum | ≤ 1 mg/L | all year | 001 |
| Flow, in conduit or thru treatment plant | daily average | ≤ .0471 MGD | all year | 001 |
| Flow, in conduit or thru treatment plant | daily maximum | ≤ .06 MGD | all year | 001 |
| E. coli | daily average | ≤ 126 CFU/100mL | all year | 001 |
| E. coli | daily maximum | ≤ 394 CFU/100mL | all year | 001 |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 7.7 lb/d | all year | 001 |
| BOD, carbonaceous [5 day, 20 C] | daily maximum | ≤ 11.8 lb/d | all year | 001 |
| pH range excursions, > 60 minutes | monthly total | ≤ 0 occur/mo | all year | 001 |
| pH range excursions, monthly total accum | monthly total | ≤ 446 min | all year | 001 |
| Oxygen demand, chem. [high level] [COD] | daily maximum | ≤ 200 mg/L | all year | 002 |
| pH | minimum | ≥ 6 SU | all year | 002 |
| pH | maximum | ≤ 9 SU | all year | 002 |
| Oil & Grease | daily maximum | ≤ 15 mg/L | all year | 002 |
| Flow, in conduit or thru treatment plant | daily average | report only (MGD) | all year | 002 |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year | 002 |
Cited limits by parameter: Texas's rules and the federal ones.
Same industry: the 165 Chemicals and Allied Products permits in Texas.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0086363 · MCP: https://passage-data.com/mcp