Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Houston, Texas. NPDES permit TX0086185, in force until May 10, 2027. Last 12 months: over a limit once (last June 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| June 2026 | E. coli, daily maximum | 534 MPN/100mL | ≤ 200 MPN/100mL | 167% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 6 mg/L | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 15 mg/L | all year |
| Solids, total suspended | daily maximum | ≤ 40 mg/L | all year |
| Solids, total suspended | daily average | ≤ 124 lb/d | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 2 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily maximum | ≤ 10 mg/L | all year |
| Nitrogen, ammonia total [as N] | daily average | ≤ 17 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .99 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 63 MPN/100mL | all year |
| E. coli | daily maximum | ≤ 200 MPN/100mL | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 7 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily maximum | ≤ 22 mg/L | all year |
| BOD, carbonaceous [5 day, 20 C] | daily average | ≤ 58 lb/d | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0086185 · MCP: https://passage-data.com/mcp