Passage Data · Check a report · Use it from your AI

Smith International Industrial Subdivision Water Supply & Sewer Services Corp

Oil And Gas Field Machinery, Houston, Texas. NPDES permit TX0084298, in force until Nov 16, 2028. Last 12 months: no values over a limit. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (42 values), form Q quarterly, form S twice a year
Last report on file
August 2026
Oct 2024 – Sep 2025
3 values over a limit, 0 required values missing, 0 of 18 reports late

Limits in force (58)

ParameterStatisticLimitMonths
BOD, 5-day, 20 deg. Cdaily average≤ 10 mg/Lall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 25 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 8.43 lb/dall year
BOD, 5-day, 20 deg. Cdaily maximum≤ 21 lb/dall year
Oxygen demand, chem. [high level] [COD]daily average≤ 100 mg/Lall year
Oxygen demand, chem. [high level] [COD]daily maximum≤ 200 mg/Lall year
Oxygen demand, chem. [high level] [COD]daily average≤ 61.7 lb/dall year
Oxygen demand, chem. [high level] [COD]daily maximum≤ 123 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 17.2 mg/Lall year
Solids, total suspendeddaily maximum≤ 42.8 mg/Lall year
Solids, total suspendeddaily average≤ 10.6 lb/dall year
Solids, total suspendeddaily maximum≤ 26.4 lb/dall year
Oil & Greasedaily average≤ 12.2 mg/Lall year
Oil & Greasedaily maximum≤ 24.5 mg/Lall year
Oil & Greasedaily average≤ 7.53 lb/dall year
Oil & Greasedaily maximum≤ 15.1 lb/dall year
Cyanide, free [amenable to chlorination]daily average≤ .062 mg/Lall year
Cyanide, free [amenable to chlorination]daily maximum≤ .138 mg/Lall year
Cyanide, free [amenable to chlorination]daily average≤ .038 lb/dall year
Cyanide, free [amenable to chlorination]daily maximum≤ .085 lb/dall year
Cadmium, total [as Cd]daily average≤ .079 mg/Lall year
Cadmium, total [as Cd]daily maximum≤ .183 mg/Lall year
Cadmium, total [as Cd]daily average≤ .048 lb/dall year
Cadmium, total [as Cd]daily maximum≤ .113 lb/dall year
Chromium, total [as Cr]daily average≤ .669 mg/Lall year
Chromium, total [as Cr]daily maximum≤ 1.248 mg/Lall year
Chromium, total [as Cr]daily average≤ .413 lb/dall year
Chromium, total [as Cr]daily maximum≤ .77 lb/dall year
Copper, total [as Cu]daily average≤ .625 mg/Lall year
Copper, total [as Cu]daily maximum≤ 1.32 mg/Lall year
Copper, total [as Cu]daily average≤ .391 lb/dall year
Copper, total [as Cu]daily maximum≤ .823 lb/dall year
Lead, total [as Pb]daily average≤ .48 mg/Lall year
Lead, total [as Pb]daily maximum≤ .92 mg/Lall year
Lead, total [as Pb]daily average≤ .302 lb/dall year
Lead, total [as Pb]daily maximum≤ .588 lb/dall year
Nickel, total [as Ni]daily average≤ 1.193 mg/Lall year
Nickel, total [as Ni]daily maximum≤ 2.277 mg/Lall year
Nickel, total [as Ni]daily average≤ .736 lb/dall year
Nickel, total [as Ni]daily maximum≤ 1.406 lb/dall year
Silver, total [as Ag]daily average≤ .077 mg/Lall year
Silver, total [as Ag]daily maximum≤ .146 mg/Lall year
Silver, total [as Ag]daily average≤ .047 lb/dall year
Silver, total [as Ag]daily maximum≤ .09 lb/dall year
Zinc, total [as Zn]daily average≤ 1.067 mg/Lall year
Zinc, total [as Zn]daily maximum≤ 2.085 mg/Lall year
Zinc, total [as Zn]daily average≤ .658 lb/dall year
Zinc, total [as Zn]daily maximum≤ 1.287 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .15 MGDall year
Flow, in conduit or thru treatment plantdaily maximum≤ .3 MGDall year
Chlorine, total residualmonthly minimum≥ .5 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 63 CFU/100mLall year
E. colidaily maximum≤ 197 CFU/100mLall year
Organics, total toxic [TTO]daily maximum≤ .298 mg/Lall year
Organics, total toxic [TTO]daily maximum≤ .184 lb/dall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Same industry: the 7 Industrial and Commercial Machinery and Computer Equipment permits in Texas.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0084298 · MCP: https://passage-data.com/mcp