Passage Data · Check a report · Use it from your AI

Veolia Es Technical Solutions LLC

Refuse Systems, Port Arthur, Texas. NPDES permit TX0083828, in force until May 21, 2029. Last 12 months: over a limit 4 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (14 values), outfall 101 form A monthly (12 values), outfall 001 form Y yearly
Last report on file
September 2026
Oct 2024 – Sep 2025
5 values over a limit, 0 required values missing, 0 of 25 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
January 2026Solids, total suspended, daily average35.75 mg/L≤ 20 mg/L79%
February 2026Solids, total suspended, daily average58 mg/L≤ 20 mg/L190%
February 2026Solids, total suspended, daily maximum70 mg/L≤ 65 mg/L8%
August 2026E. coli, daily maximum435 CFU/100mL≤ 399 CFU/100mL9%

Limits in force (28)

ParameterStatisticLimitMonthsOutfall
Oxygen demand, chem. [high level] [COD]daily maximum≤ 200 mg/Lall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Oil & Greasedaily maximum≤ 15 mg/Lall year001
Carbon, tot organic [TOC]daily maximum≤ 75 mg/Lall year001
Arsenic, total [as As]daily maximum≤ .3 mg/Lall year001
Cadmium, total [as Cd]daily maximum≤ .0016 mg/Lall year001
Chromium, total [as Cr]daily maximum≤ .5 mg/Lall year001
Copper, total [as Cu]daily maximum≤ .0377 mg/Lall year001
Lead, total [as Pb]daily maximum≤ .0193 mg/Lall year001
Zinc, total [as Zn]daily maximum≤ .466 mg/Lall year001
Aluminum, total [as Al]daily maximum≤ 7.3 mg/Lall year001
Phenolsdaily maximum≤ .5 mg/Lall year001
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Mercury, total [as Hg]daily maximum≤ .00044 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily average≤ 20 mg/Lall year101
BOD, 5-day, 20 deg. Cdaily maximum≤ 65 mg/Lall year101
pHminimum≥ 6 SUall year101
pHmaximum≤ 9 SUall year101
Solids, total suspendeddaily average≤ 20 mg/Lall year101
Solids, total suspendeddaily maximum≤ 65 mg/Lall year101
Flow, in conduit or thru treatment plantdaily average≤ .01 MGDall year101
Flow, in conduit or thru treatment plantdaily maximum≤ .02 MGDall year101
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year101
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year101
E. colidaily average≤ 126 CFU/100mLall year101
E. colidaily maximum≤ 399 CFU/100mLall year101

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Same industry: the 13 Refuse Systems permits in Texas.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0083828 · MCP: https://passage-data.com/mcp