Passage Data · Check a report · Use it from your AI

West Harris County Mud 10

Sewage treatment plant, major discharger, Houston, Texas. NPDES permit TX0082317, in force until Mar 6, 2028. Last 12 months: over a limit 2 times (last November 2025), 1 of 17 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (20 values), outfall TX1 form Q quarterly (28 values), outfall TXA form S twice a year
Renewal application due
Sep 8, 2027 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
1 value over a limit, 0 required values missing, 0 of 18 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
October 2025E. coli, daily maximum2420 MPN/100mL≤ 200 MPN/100mL1110%
November 2025Chlorine, total residual, instantaneous maximum.11 mg/L< .1 mg/L10%

Limits in force (55)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Solids, total suspendeddaily average≤ 15 mg/Lall year001
Solids, total suspendeddaily maximum≤ 40 mg/Lall year001
Solids, total suspendeddaily average≤ 188 lb/dall year001
Nitrogen, ammonia total [as N]daily average≤ 3 mg/LApr–Oct001
Nitrogen, ammonia total [as N]daily average≤ 5 mg/LJan, Feb, Mar, Nov, Dec001
Nitrogen, ammonia total [as N]daily maximum≤ 10 mg/LApr–Oct001
Nitrogen, ammonia total [as N]daily maximum≤ 10 mg/LJan, Feb, Mar, Nov, Dec001
Nitrogen, ammonia total [as N]daily average≤ 38 lb/dApr–Oct001
Nitrogen, ammonia total [as N]daily average≤ 63 lb/dJan, Feb, Mar, Nov, Dec001
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Flow, in conduit or thru treatment plant2-hour peak≤ 4167 gal/minall year001
Flow, in conduit or thru treatment plantannual average≤ 1.5 MGDall year001
Chlorine, total residualinstantaneous maximum< .1 mg/Lall year001
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year001
E. colidaily average≤ 63 MPN/100mLall year001
E. colidaily maximum≤ 200 MPN/100mLall year001
BOD, carbonaceous [5 day, 20 C]daily average≤ 10 mg/Lall year001
BOD, carbonaceous [5 day, 20 C]daily maximum≤ 25 mg/Lall year001
BOD, carbonaceous [5 day, 20 C]daily average≤ 125 lb/dall year001
Whole effluent toxicity - retest #17-day minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #27-day minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Survival Test Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
NOEC Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
NOEC Sub-Lethal Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelas7-day minimumreport only (pass=0;fail=1)all yearTX1
Pass/Fail Sub-Lethal Static Renewal 7 Day Chronic Pinephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
LOEC Lethal Survival Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubia7-day minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Ceriodaphnia dubiamonthly average minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelas7-day minimumreport only (%)all yearTX1
LOEC Sub-Lethal Reproduction Static Renewal 7 Day Chronic Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Whole effluent toxicity - retest #1single samplereport only (pass=0;fail=1)all yearTXA
Whole effluent toxicity - retest #2single samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute D. Pulexsingle samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXA

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0082317 · MCP: https://passage-data.com/mcp