Passage Data · Check a report · Use it from your AI

Fort Bend County Mud 30

Sewage treatment plant, major discharger, Houston, Texas. NPDES permit TX0078751, in force until Feb 23, 2028. Last 12 months: over a limit 5 times (last May 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (18 values), outfall TX1 form Q quarterly (16 values), outfall TXA form S twice a year
Renewal application due
Aug 27, 2027 · 180 days before expiry; your permit may set another date
Last report on file
September 2026
Oct 2024 – Sep 2025
0 values over a limit, 0 required values missing, 0 of 18 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
October 2025E. coli, daily maximum727 CFU/100mL≤ 200 CFU/100mL264%
January 2026Nitrogen, ammonia total [as N], daily average7.36 mg/L≤ 3 mg/L145%
January 2026Nitrogen, ammonia total [as N], daily average75.29 lb/d≤ 38 lb/d98%
January 2026Nitrogen, ammonia total [as N], daily maximum20 mg/L≤ 10 mg/L100%
May 2026E. coli, daily maximum490 CFU/100mL≤ 200 CFU/100mL145%

Limits in force (38)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Solids, total suspendeddaily average≤ 15 mg/Lall year001
Solids, total suspendeddaily maximum≤ 40 mg/Lall year001
Solids, total suspendeddaily average≤ 188 lb/dall year001
Nitrogen, ammonia total [as N]daily average≤ 3 mg/Lall year001
Nitrogen, ammonia total [as N]daily maximum≤ 10 mg/Lall year001
Nitrogen, ammonia total [as N]daily average≤ 38 lb/dall year001
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Flow, in conduit or thru treatment plant2-hour peak≤ 4167 gal/minall year001
Flow, in conduit or thru treatment plantannual average≤ 1.5 MGDall year001
E. colidaily average≤ 63 CFU/100mLall year001
E. colidaily maximum≤ 200 CFU/100mLall year001
BOD, carbonaceous [5 day, 20 C]daily average≤ 10 mg/Lall year001
BOD, carbonaceous [5 day, 20 C]daily maximum≤ 25 mg/Lall year001
BOD, carbonaceous [5 day, 20 C]daily average≤ 125 lb/dall year001
Whole effluent toxicity - retest #148-hour minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #1monthly average minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #248-hour minimumreport only (pass=0;fail=1)all yearTX1
Whole effluent toxicity - retest #2monthly average minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex48-hour minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulexmonthly average minimumreport only (pass=0;fail=1)all yearTX1
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (pass=0;fail=1)all yearTX1
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulex48-hour minimumreport only (%)all yearTX1
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulexmonthly average minimumreport only (%)all yearTX1
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelas48-hour minimumreport only (%)all yearTX1
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelasmonthly average minimumreport only (%)all yearTX1
LOAEC Lethal Static Renewal 48HR Acute Daphnia pulex48-hour minimumreport only (%)all yearTX1
LOAEC Lethal Static Renewal 48HR Acute Daphnia pulexmonthly average minimumreport only (%)all yearTX1
LOAEC Lethal Survival Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (%)all yearTX1
LOAEC Lethal Survival Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (%)all yearTX1
Whole effluent toxicity - retest #1single samplereport only (pass=0;fail=1)all yearTXA
Whole effluent toxicity - retest #2single samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute D. Pulexsingle samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXA

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0078751 · MCP: https://passage-data.com/mcp