Passage Data · Check a report · Use it from your AI

Abbott, City of

Sewage treatment plant, Abbott, Texas. NPDES permit TX0075396, in force until Apr 19, 2029. Last 12 months: over a limit 13 times (last March 2026), 1 of 11 reports late. Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (12 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
28 values over a limit, 48 required values missing, 10 of 12 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

All 13 values over a limit
Period endingParameterReportedLimitOver by
October 2025BOD, 5-day, 20 deg. C, daily average33.25 mg/L≤ 30 mg/L11%
October 2025Solids, total suspended, daily average90.25 mg/L≤ 90 mg/L0%
October 2025pH, maximum9.3 SU≤ 9 SU—
November 2025Solids, total suspended, daily average98.75 mg/L≤ 90 mg/L10%
November 2025pH, maximum9.5 SU≤ 9 SU—
December 2025BOD, 5-day, 20 deg. C, daily average31 mg/L≤ 30 mg/L3%
December 2025E. coli, colony forming units [CFU], daily average333.66 CFU/100mL≤ 126 CFU/100mL165%
December 2025E. coli, colony forming units [CFU], single grab sample1300 CFU/100mL≤ 399 CFU/100mL226%
January 2026BOD, 5-day, 20 deg. C, daily average39 mg/L≤ 30 mg/L30%
February 2026BOD, 5-day, 20 deg. C, daily average17.76 lb/d≤ 13 lb/d37%
February 2026BOD, 5-day, 20 deg. C, daily average46.25 mg/L≤ 30 mg/L54%
February 2026pH, maximum9.3 SU≤ 9 SU—
March 2026BOD, 5-day, 20 deg. C, daily average41.6 mg/L≤ 30 mg/L39%

Limits in force (12)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 4 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 30 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 100 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 13 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 90 mg/Lall year
Solids, total suspendeddaily average≤ 38 lb/dall year
Flow, in conduit or thru treatment plantdaily average≤ .05 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
E. coli, colony forming units [CFU]daily average≤ 126 CFU/100mLall year
E. coli, colony forming units [CFU]single grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0075396 · MCP: https://passage-data.com/mcp