Passage Data · Check a report · Use it from your AI

Rio Grande City, City of

Sewage treatment plant, major discharger, Rio Grande City, Texas. NPDES permit TX0068764, in force until Jun 4, 2029. Last 12 months: over a limit 5 times (last June 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: outfall 001 form A monthly (17 values), outfall TX1 form Q quarterly (12 values), outfall TXA form S twice a year
Last report on file
September 2026
Oct 2024 – Sep 2025
7 values over a limit, 0 required values missing, 2 of 18 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
April 2026E. coli, daily average759.825 CFU/100mL≤ 126 CFU/100mL503%
April 2026E. coli, daily maximum2419.6 CFU/100mL≤ 399 CFU/100mL506%
May 2026E. coli, daily average153.875 CFU/100mL≤ 126 CFU/100mL22%
May 2026E. coli, daily maximum547.5 CFU/100mL≤ 399 CFU/100mL37%
June 2026Flow, in conduit or thru treatment plant, 2-hour peak2202 gal/min≤ 2041 gal/min8%

Limits in force (31)

ParameterStatisticLimitMonthsOutfall
Oxygen, dissolved [DO]monthly minimum≥ 2 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily average≤ 20 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily maximum≤ 45 mg/Lall year001
BOD, 5-day, 20 deg. Cdaily average≤ 250 lb/dall year001
pHminimum≥ 6 SUall year001
pHmaximum≤ 9 SUall year001
Solids, total suspendeddaily average≤ 20 mg/Lall year001
Solids, total suspendeddaily maximum≤ 45 mg/Lall year001
Solids, total suspendeddaily average≤ 250 lb/dall year001
Flow, in conduit or thru treatment plantdaily averagereport only (MGD)all year001
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year001
Flow, in conduit or thru treatment plant2-hour peak≤ 2041 gal/minall year001
Flow, in conduit or thru treatment plantannual average≤ 1.5 MGDall year001
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year001
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year001
E. colidaily average≤ 126 CFU/100mLall year001
E. colidaily maximum≤ 399 CFU/100mLall year001
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulex48-hour minimumreport only (pass=0;fail=1)all yearTX1
Low Flow Pass/Fail Static Renewal 48Hr Acute Daphnia pulexmonthly average minimumreport only (pass=0;fail=1)all yearTX1
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (pass=0;fail=1)all yearTX1
LF Pass/Fail Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (pass=0;fail=1)all yearTX1
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulex48-hour minimumreport only (%)all yearTX1
NOAEC Lethal Statis Renewal 48 Hr Acute Daphnia pulexmonthly average minimumreport only (%)all yearTX1
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelas48-hour minimumreport only (%)all yearTX1
NOAEC Lethal Static Renewal 48Hr acute Pimephales promelasmonthly average minimumreport only (%)all yearTX1
LOAEC Lethal Static Renewal 48HR Acute Daphnia pulex48-hour minimumreport only (%)all yearTX1
LOAEC Lethal Static Renewal 48HR Acute Daphnia pulexmonthly average minimumreport only (%)all yearTX1
LOAEC Lethal Survival Static Renewal 48Hr Acute Pimephales promelas48-hour minimumreport only (%)all yearTX1
LOAEC Lethal Survival Static Renewal 48Hr Acute Pimephales promelasmonthly average minimumreport only (%)all yearTX1
LC50 Pass/Fail Static 24Hr Acute D. Pulexsingle samplereport only (pass=0;fail=1)all yearTXA
LC50 Pass/Fail Static 24Hr Acute Pimephales promelassingle samplereport only (pass=0;fail=1)all yearTXA

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0068764 · MCP: https://passage-data.com/mcp