Passage Data · Check a report · Use it from your AI
Sewage treatment plant, Wallis, Texas. NPDES permit TX0068713, in force until Jun 6, 2030. Last 12 months: over a limit 8 times (last June 2026), 2 of 16 reports late. Source: EPA ECHO, Oct 22, 2026.
| Period ending | Parameter | Reported | Limit | Over by |
|---|---|---|---|---|
| November 2025 | Oxygen, dissolved [DO], monthly minimum | 2 mg/L | ≥ 3 mg/L | 33% |
| January 2026 | Flow, in conduit or thru treatment plant, daily average | .02877 MGD | ≤ .025 MGD | 15% |
| February 2026 | Flow, in conduit or thru treatment plant, daily average | .04429 MGD | ≤ .025 MGD | 77% |
| February 2026 | Solids, total suspended, daily average | 26.25 mg/L | ≤ 20 mg/L | 31% |
| March 2026 | Flow, in conduit or thru treatment plant, daily average | .05474 MGD | ≤ .025 MGD | 119% |
| April 2026 | Flow, in conduit or thru treatment plant, daily average | .0607 MGD | ≤ .025 MGD | 143% |
| May 2026 | Flow, in conduit or thru treatment plant, daily average | .0671 MGD | ≤ .025 MGD | 168% |
| June 2026 | Flow, in conduit or thru treatment plant, daily average | .06346 MGD | ≤ .025 MGD | 154% |
| Parameter | Statistic | Limit | Months |
|---|---|---|---|
| Oxygen, dissolved [DO] | monthly minimum | ≥ 3 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 20 mg/L | all year |
| BOD, 5-day, 20 deg. C | single grab sample | ≤ 65 mg/L | all year |
| BOD, 5-day, 20 deg. C | daily average | ≤ 4.2 lb/d | all year |
| pH | minimum | ≥ 6 SU | all year |
| pH | maximum | ≤ 9 SU | all year |
| Solids, total suspended | daily average | ≤ 20 mg/L | all year |
| Solids, total suspended | single grab sample | ≤ 65 mg/L | all year |
| Solids, total suspended | daily average | ≤ 4.2 lb/d | all year |
| Flow, in conduit or thru treatment plant | daily average | ≤ .025 MGD | all year |
| Flow, in conduit or thru treatment plant | daily maximum | report only (MGD) | all year |
| Chlorine, total residual | monthly minimum | ≥ 1 mg/L | all year |
| Chlorine, total residual | monthly maximum | ≤ 4 mg/L | all year |
| E. coli | daily average | ≤ 126 CFU/100mL | all year |
| E. coli | single grab sample | ≤ 399 CFU/100mL | all year |
Cited limits by parameter: Texas's rules and the federal ones.
· Save this facility as a site · Superfund sites nearby · Your permits on one board
On EPA ECHO: Facility report · DMR history
Your permit document is the final word. As JSON: /api/v1/permits/TX0068713 · MCP: https://passage-data.com/mcp