Passage Data · Check a report · Use it from your AI

Ellinger Sewer and Water Supply Corporation

Sewerage Systems, Ellinger, Texas. NPDES permit TX0066648, in force until Jun 13, 2030. Last 12 months: over a limit 6 times (last August 2026). Source: EPA ECHO, Oct 22, 2026.

Reports due
About 20 days after each period: form A monthly (16 values), form Q quarterly (2 values)
Last report on file
August 2026
Oct 2024 – Sep 2025
0 values over a limit, 3 required values missing, 0 of 16 reports late

Last 12 months (Oct 1, 2025 – Sep 30, 2026)

Period endingParameterReportedLimitOver by
April 2026Flow, in conduit or thru treatment plant, daily average.052 MGD≤ .046 MGD13%
May 2026Solids, total suspended, daily average231 mg/L≤ 20 mg/L1055%
May 2026Solids, total suspended, daily average260 lb/d≤ 7.7 lb/d3277%
May 2026Solids, total suspended, single grab sample1090 mg/L≤ 65 mg/L1577%
July 2026Flow, in conduit or thru treatment plant, daily average.049 MGD≤ .046 MGD7%
August 2026Solids, total suspended, daily average25.9 mg/L≤ 20 mg/L30%

Limits in force (18)

ParameterStatisticLimitMonths
Oxygen, dissolved [DO]monthly minimum≥ 3 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 20 mg/Lall year
BOD, 5-day, 20 deg. Csingle grab sample≤ 65 mg/Lall year
BOD, 5-day, 20 deg. Cdaily average≤ 7.7 lb/dall year
pHminimum≥ 6 SUall year
pHmaximum≤ 9 SUall year
Solids, total suspendeddaily average≤ 20 mg/Lall year
Solids, total suspendedsingle grab sample≤ 65 mg/Lall year
Solids, total suspendeddaily average≤ 7.7 lb/dall year
Nitrogen, ammonia total [as N]daily averagereport only (mg/L)all year
Nitrogen, ammonia total [as N]single grab samplereport only (mg/L)all year
Nitrogen, ammonia total [as N]daily averagereport only (lb/d)all year
Flow, in conduit or thru treatment plantdaily average≤ .046 MGDall year
Flow, in conduit or thru treatment plantdaily maximumreport only (MGD)all year
Chlorine, total residualmonthly minimum≥ 1 mg/Lall year
Chlorine, total residualmonthly maximum≤ 4 mg/Lall year
E. colidaily average≤ 126 CFU/100mLall year
E. colisingle grab sample≤ 399 CFU/100mLall year

How strict are these limits?

Cited limits by parameter: Texas's rules and the federal ones.

Check this month's numbers Email me before each report is due

· Save this facility as a site · Superfund sites nearby · Your permits on one board

On EPA ECHO: Facility report · DMR history

Your permit document is the final word. As JSON: /api/v1/permits/TX0066648 · MCP: https://passage-data.com/mcp